24
12.5
Description of “Voltage control line 1 S.Q1” menu
In this paragraph control parameters, thresholds setting and control levels of power sources defining acceptability criteria
are described. In this menu is also possible set the insensibility level to micro interruptions using parameter P06.10 (stan-
dard value 100ms). This could be extended until 30s in case of disturbed lines.
Fig. 35
CLOSED
OPENED
P06.04
P06.05
P06.02
P06.01
V MAIN
LOGIC
STATUS
BREAKER
STATUS
P06.03
P06.06 P06.03
N.B. the insensibility to interruption is for default 100ms. With parameter P06.10 this time could be modify until 30s.
M06 –
VOLTAGE CONTROL LINE 1 S.Q1
UoM
DEFAULT
RANGE
P06.01 MIN voltage limit for trip
%
85
70-100
P06.02 MIN voltage restore
%
90
70-100
P06.03 MIN voltage delay
s
5
0-600
P06.04 MAX voltage limit for trip
%
115
100-130 / OFF
P06.05 MAX voltage restore
%
110
100-130 / OFF
P06.06 MAX voltage delay
s
5
0-600
P06.07 Return of power in the limits delayed
(when S.Q2 source not available)
s
10
1-6000
P06.08 Return of power in the limits delayed
(when S.Q2 source available)
s
60
1-6000
P06.09 Phase failure threshold
%
70
60% - 80%
OFF
P06.10 Phase failure delay
s
0.1
0.1s-30s
P06.11 MAX Asymmetry limit
%
15
1% -20%/OFF
P06.12 MAX Asymmetry delay
s
5
0.1-900
P06.13 MAX frequency limit
%
105
100-120/OFF
P06.14 MAX frequency delay
s
3
0-600
P06.15 MIN frequency limit
%
95
OFF/80-100
P06.16 MIN frequency delay
s
5
0-600
P06.17 S.Q1 control OFF mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P06.18 S.Q1 control MAN mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P06.19 Time delay generator starter due to a
lack of S.Q1
s
OFF
OFF / 1-6000
P06.20 Generator cooling time
s
120
1-3600
12. Parameters