12.12
Alarm description
CODE DESCRIPTION
ALARM EXPLANATION
A01
Q1 (Line 1) timeout
The Q1 changeover device did not perform the opening or clo-
sing operation within the max. time set. After alarm A03 genera-
tion, the opening or closing command is inhibited.
Alarms are generated only if at least one of the two power
sources S.Q1 or S.Q2 are present.
A02
Q2 (Line 2) timeout
The Q2 changeover device did not perform the opening or clo-
sing operation within the max. time set. After alarm A04 genera-
tion, the opening or closing command is inhibited.
Alarms are generated only if at least one of the two power
sources S.Q1 or S.Q2 are present.
A03
S.Q1 (Line 1) wrong phase sequence
The phase sequence recorded on S.Q1 (line 1) does not corre-
spond to the one programmed.
A04
S.Q2 (Line 2) wrong phase sequence
The phase sequence recorded on S.Q2 (line 2) does not corre-
spond to the one programmed.
A05
Load not powered timeout
The load has been without power for a time longer than the
maximum specified with P05.11, either because both source
lines (S.Q1 and S.Q2) were absent or because both Q1 and Q2
remained open.
A06
Emergency
Alarm generated by the opening of the external input with
Emergency function. Both Q1 and Q2will be opened.
A07
Intervention for protection CTR Q1
Q1 (Line 1) has tripped because of a plant protection( contact
CTR), signalled by activation of the input with function Line 1
breaker protection trip.
A08
Intervention for protection CTR Q2
Q2 (Line 2) has tripped because of a plant protection (contact
CTR), signalled by activation of the input with function Line 2
breaker protection trip.
A09
S.Q1 Line 1 generator not available
Alarm generated by the input Generator S.Q1 (Line 1) ready.
A10
S.Q2 Line 2 generator not available
Alarm generated by the input Generator S.Q2 (Line 2) ready.
A11
Maintenance operations S.Q1
Alarm generated when the number of operations for S.Q1 reach
the value sated in the menu M12. Use the menu commands to
restore the function and to reset the alarm.
A12
Maintenance operations S.Q2
Alarm generated when the number of operations for S.Q2 reach
the value sated in the menu M12. Use the menu commands to
restore the function and to reset the alarm.