Automatic transfer switch
4 226 81
Installa
tion and user manual
33
FUNCTION
DESCRIPTION
External S.Q2 control
Line 2 voltage control signal from external device. Ena-
bled, it indicates the voltage is within the limits
Enable Load on S.Q1
It allows load connection on S.Q1, in addition to internal
controls.
Enable Load on S.Q2
Like previous, referred to S.Q2
Delay 1 bypass
Reset the delay presence on S.Q1
Delay 2 bypass
Reset the delay presence on S.Q2
Keypad lock
If closed, it locks all the functions from front keypad except
measure viewing
Lock Parameters
If closed, it locks the access to setup menus
Lock remote control
If closed, it locks write access through serial interface ports
Siren OFF
It disables the siren
Alarms inhibition
If enabled, it disables the alarms that have the property
Inhibit alarms activated
Alarms reset
It resets the retained alarms for which the condition that
triggered the same has stopped
Key OFF simulation
Closing the input is the equivalent of pressing the key.
Key MAN simulation
Closing the input is the equivalent of pressing the key.
Key AUT simulation
Closing the input is the equivalent of pressing the key.
Automatic test inhibition
It inhibits the automatic test
LED Test
It makes all the LEDS on the front panel flash
Q1 closing
Close the Q1 in manual mode
Q1 opening
Open the Q1 in manual mode
Q1 toggling
Toggle the Q1 in manual mode
Q2 closing
Close the Q2 in manual mode
Q2 opening
Open the Q2 in manual mode
Q2 toggling
Toggle the Q2 in manual mode