background image

Cat. no(s).:  882 30

Configuration tool with screen

Technical data sheet: F01163EN/00

Updated on: 

Created on: 23/08/2010

3/5

CONTENTS

A

 Calibration

In order to set this calibration, it is necessary to measure the surrounding light 
level using a luxmeter beforehand. The surrounding light level measured will 
then have to be transmitted to the detector.
Steps for regulating the electric light factor:
- Put the light on and close the shutters 
- Wait 2 minutes
-  Measure the light level below the cell using a luxmeter
Enter this value into the tool and send it to the cell. This calibration will be 
acknowledged during the next detection cycle.

B

 Light regulation

Principle: the Light regulation allows users to distinguish between the 
contribution from natural light and that from artificial light.
It can be used for continuous measurement of the natural light level (daylight) 
and for compensating for the lack of this natural light level by switching on the 
artificial light. 
The light level cell makes a distinction between the contribution from natural light 
and that from artificial light and, by comparing with the Daylight setpoint, the 
product adjusts the contribution from artificial light.
The Daylight setpoint set in the products is a threshold below which the 
illuminated area may not go as indicated in standard NF 12464-1. 

C

 Provision of light

This is that quantity of additional lux brought in by switching on the artificial light.

3. NAVIGATION (continued)

3.2 Instructions for use (continued)
3.2.1. Sensor parameters (continued)

A

 Time delay

Length of time the load is on after a detection is made. See technical data sheet 
for the associated detector.

B

 Sensitivity

 

Setting the detector range (see technical data sheet for the associated detector).

C

 Daylight setpoint

Value at which the load comes on if light is less than the Light regulation and 
goes off if it is above this threshold. The Daylight setpoint can be set up to a 
maximum of 1275 lux.

D

 Mode

There are 4 different operating modes.
Auto on/Auto off mode: 
Comes on automatically: 
- At the detection of a presence if there is an insufficient natural level of light. 
Turns off automatically: 
- If no presence is detected and at the end of the time delay set. 
- Or if there is a sufficient level of natural light (activated Light regulation). 
Any new detection causes an automatic switch on if there is insufficient light.
Walkthrough:
-  If there is no presence detected in the 3 minutes following an initial detection, 

the detector will cut off after 3 minutes.

-  If a new presence is detected in the 3 minutes following the initial detection, the 

device will cut off at the end of the time delay set.

Manual on/Auto off mode: 
Comes on via a manual switch, automatic switch off: 
-  Where no presence is detected and at the end of the time delay set.
Following switch off, any new detection within a 30-second period will cause the 
device to be switched on automatically.
After 30 seconds the device is switched on via a manual switch.
Partial on/Group off mode:
This mode is used to ungroup circuits that are switched on upon detection and 
the circuits which will be switched off at the end of the detection.
Example: Upon detection I switch on the main lighting and I can control 
occasional lighting manually in parallel. At the end of the detection, the detector 
orders the main lighting and the occasional lighting circuits to be switched off.

E

 Detection scheme

This menu is intended for PIR/US dual technology detectors. There are 
4 combination types possible.
PIR and US: the detector needs both technologies in order for it to be switched 
on.
PIR or US: the detector needs one of these technologies in order for it to be 
switched on.
PIR only: the detector needs PIR technology in order for it to be switched on.
US only: the detector needs US technology in order for it to be switched on.

F

 Alert

A "BEEP" is transmitted before the end of the time delay programmed.

3. NAVIGATION (continued)

3.2 Instructions for use (continued)
3.2.2. Advanced mode

Light regulation

Light regulation

B

Sensor parameter

Advanced mode

Files

PnL sensor

Advanced mode

2

Calibration

Light regulation

Provision of light

Loop type

A

D

C

B

Max. lux : 99 995

Calibration

0000 Lux

A

Max. lux :1275

Provision of light

1275 Lux

C

Closed loop
Open loop

Loop type

Closed loop

D

Note:  

All technical information is available at

 

www.legrandoc.com

Summary of Contents for 882 30

Page 1: ...BUS products Push Learn 2 TECHNICAL FEATURES Infra red communication technology 4 m max In the direction of the product to be measured At a 15 angle limit in the axis of the PIR transmission and reception LED see image Backlight screen automatic switch off Weight 71 g Impact resistance IK04 Operating temperature 5 C to 45 C Storage temperature 20 C to 70 C CONTENTS Page 1 Use 1 2 Technical feature...

Page 2: ...ed above 3 NAVIGATION continued 3 2 Instructions for use Sensor parameters Advanced mode Files PnL sensor Files PnL sensor Test Settings ON 2 3 sec 1 2 3 5 4 6 3 2 1 Sensor parameters Sensor parameter Advanced mode Files PnL sensor Sensor parameters 1 Time delay 000 H 15 Min 00 Sec Max time delay 255 H 59 Min 59 Sec A Daylight setpoint 0500 Lux Max 1275 Lux C Sensitivity Very high US High PIR Very...

Page 3: ...ce if there is an insufficient natural level of light Turns off automatically If no presence is detected and at the end of the time delay set Or if there is a sufficient level of natural light activated Light regulation Any new detection causes an automatic switch on if there is insufficient light Walkthrough If there is no presence detected in the 3 minutes following an initial detection the dete...

Page 4: ...o check how the installation is operating When the command is sent the detector goes into test mode for 5 minutes The detector is therefore in Auto ON Auto OFF mode and the time delay is set at 5 sec End time delay Used for forcing the end of the current time delay Initial state Used for exiting the Test mode and puts the installation into operating mode initial state This function does not modify...

Page 5: ... at night 20 70 lux Living premises 100 200 lux Well lit apartment 200 400 lux Working premises 200 3 000 lux Stadium at night 1 500 lux Outside with cloudy sky 25 000 lux Outside in full sunshine 50 000 to 100 000 lux 5 MAINTENANCE Do not use acetone tar removing cleaning agents or trichloroethylene Maintenance with the following products Hexane EN 60669 1 Methylated spirit Soapy water Diluted am...

Reviews: