Archimod HE 240-480®
Installa
tion and main
tenanc
e manual
11
WARNING
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be
observed when working on batteries:
a) remove watches, rings or other metal objects.
b) use tools with insulated handles.
c) wear rubber gloves and boots.
d) do not lay tools or metal parts on top of batteries.
e) disconnect the charging source prior to connecting or disconnecting battery terminals.
f ) determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not
having a grounded supply circuit).
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. The batteries
installed inside the cabinet must be disposed of correctly. For the disposal requirements refer to local laws and relevant
standards.
CAUTION
The UPS functions with TT and TN systems.
It has a pass-through neutral architecture: the status of the neutral on
output is the same as the neutral on input.
When the output load needs a different neutral status from the input status, it is necessary to place downstream of the
UPS a suitably scaled isolation transformer protected in compliance with the standards in force.
CAUTION
Do not open the battery fuse holders of the external battery units while the UPS is powering the loads in stored energy
mode.
WARNING
To reduce the risk of fire or electric shock, the UPS must work in closed, clean environments with controlled temperature
and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must not be
above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing.
CAUTION
The equipment generates, uses and can radiate radio frequency energy, If it is not installed and used in accordance with
the instructions, it may cause harmful interference with radio communications.
Archimod HE 240-480 is a category C3 UPS according to the standard EN62040-2.
The UPS can be used in commercial and industrial environments; nevertheless restrictions or adequate countermeasures
might be necessary to avoid radio interference.
The qualified technician must also perform the following installation:
- Archimod HE 240: pass the input and output cable connections through two toroidal cores N30 material R 202 x 153 x
25 mm.
- Archimod HE 480: pass the input and output cable connections through four toroidal cores N30 material R 202 x 153 x
25 mm.
Summary of Contents for Archimod HE 240
Page 1: ...Archimod HE 240 480 Installation and maintenance manual Item LE09392AA 12 16 01 CT ...
Page 2: ...2 EN ENGLISH 3 Archimod HE 240 480 ...
Page 14: ...14 3 Models ...
Page 15: ...Archimod HE 240 480 Installation and maintenance manual 15 Block diagram ...
Page 18: ...18 3 Models ...
Page 19: ...Archimod HE 240 480 Installation and maintenance manual 19 Block diagram ...
Page 23: ...Archimod HE 240 480 Installation and maintenance manual 23 ...
Page 24: ...24 4 Installation ...
Page 25: ...Archimod HE 240 480 Installation and maintenance manual 25 ...
Page 26: ...26 4 Installation ...
Page 27: ...Archimod HE 240 480 Installation and maintenance manual 27 ...
Page 28: ...28 4 Installation ...
Page 33: ...Archimod HE 240 480 Installation and maintenance manual 33 Archimod HE 240 ...
Page 36: ...36 Archimod HE 240 4 Installation ...
Page 41: ...Archimod HE 240 480 Installation and maintenance manual 41 Archimod HE 240 ...
Page 70: ...70 ...
Page 71: ...Archimod HE 240 480 Installation and maintenance manual 71 ...