34
Archimod HE 480
The UPS negative pole battery busbars are in common and must always remain in this status.
The UPS positive pole battery busbars are connected in parallel by means of a plate. The factory connection has strings
of batteries in common.
To install independent strings of batteries remove the plate and make the configuration from the control panel to the end
of the UPS installation as described in the paragraph 5.5.
The positive pole battery busbars are marked as follows:
-
+0: connected to the power modules controlled by the CM0 command board;
-
+1: connected to the power modules controlled by the CM1 command board;
-
+2: connected to the power modules controlled by the CM2 command board;
-
+3: connected to the power modules controlled by the CM3 command board.
4. Installation
Summary of Contents for Archimod HE 240
Page 1: ...Archimod HE 240 480 Installation and maintenance manual Item LE09392AA 12 16 01 CT ...
Page 2: ...2 EN ENGLISH 3 Archimod HE 240 480 ...
Page 14: ...14 3 Models ...
Page 15: ...Archimod HE 240 480 Installation and maintenance manual 15 Block diagram ...
Page 18: ...18 3 Models ...
Page 19: ...Archimod HE 240 480 Installation and maintenance manual 19 Block diagram ...
Page 23: ...Archimod HE 240 480 Installation and maintenance manual 23 ...
Page 24: ...24 4 Installation ...
Page 25: ...Archimod HE 240 480 Installation and maintenance manual 25 ...
Page 26: ...26 4 Installation ...
Page 27: ...Archimod HE 240 480 Installation and maintenance manual 27 ...
Page 28: ...28 4 Installation ...
Page 33: ...Archimod HE 240 480 Installation and maintenance manual 33 Archimod HE 240 ...
Page 36: ...36 Archimod HE 240 4 Installation ...
Page 41: ...Archimod HE 240 480 Installation and maintenance manual 41 Archimod HE 240 ...
Page 70: ...70 ...
Page 71: ...Archimod HE 240 480 Installation and maintenance manual 71 ...