6.1
Warehousing
The UPS must be stored in an environment with a room temperature between 0°C (+32°F) and
+50°C (+122°F) and humidity less than 90% (not condensing).
The UPSs Daker DK Plus 3 101 73 et 3 101 74 must be stored in an environment with a room tem-
perature b20°C (+68°F) and +25°C (+77°F) to ensure an optimal battery life.
The batteries installed inside the UPS are lead/acid sealed and do not require maintenance (VRLA).
The batteries should be charged for 12 hours every 3 months by connecting the UPS to the utility
supply and switching on the utility input breaker located on the UPS rear panel. Repeat this proce-
dure every two months if the storage ambient temperature is above +25°C (+77°F).
CAUTION
The UPS must never be stored if the batteries are partially or totally discharged.
LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing.
6.2
Dismantling
DANGER
Dismantling and disposal operations may only be done by a qualified electrician. These instruc-
tions are to be considered indicative: in every country there are different regulations with regard
to the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere
to the standards in force in the country where the equipment is used.
Do not throw any component of the equipment in the ordinary rubbish.
Batteries must be disposed of in a site intended for the recovery of toxic waste. Disposal in the
traditional rubbish is not allowed.
Apply to the competent agencies in your countries for the proper procedure.
WARNING
A battery may constitute a risk of an electric shock and high short-circuit current.
When working on batteries, the prescriptions indicated in chapter 2 are to be adhered to.
It is important to dismantle the various parts the UPS consists of. For these operations, Personal
Protective Equipment must be worn.
Sub-divide the components separating the metal from the plastic, from the copper and so on ac-
cording to the type of selective waste disposal in the country where the UPS is dismantled.
If the dismantled components must be stored before being properly disposed, be careful to keep
them in a safe place protected from atmospheric agents to avoid soil and groundwater contamination.
For the disposal of electronic waste it is necessary to refer to the industry standards.
6 Warehousing and dismantling
Summary of Contents for DAKER DK Plus 3 101 73
Page 10: ...10 3 2 2 Onduleur armoire batteries option 3 Installation Phase 1 Phase 2 ...
Page 12: ...12 3 Installation Phase 5 Phase 6 ...
Page 38: ...38 ...
Page 46: ...46 3 2 2 UPS battery cabinet optional 3 Installation Step 1 Step 2 ...
Page 48: ...48 3 Installation Step 5 Step 6 ...
Page 74: ...74 ...
Page 82: ...82 3 2 2 UPS armadio batterie opzionale Fase 1 Fase 2 3 Installazione ...
Page 84: ...84 Fase 5 Fase 6 3 Installazione ...
Page 110: ...110 ...
Page 118: ...118 118 3 2 2 USV Batterieschrank Optional 3 Installation Schritt 1 Schritt 2 ...
Page 120: ...120 3 Installation Schritt 5 Schritt 6 ...
Page 146: ...146 ...
Page 154: ...154 154 3 2 2 SAI armario de la batería opcional 3 Instalación Paso 1 Paso 2 ...
Page 156: ...156 3 Instalación Paso 5 Paso 6 ...
Page 182: ...182 ...
Page 190: ...190 190 3 2 2 ИБП батарейный модуль опциональный 3 Монтаж Шаг 1 Шаг 2 ...
Page 192: ...192 3 Монтаж Шаг 5 Шаг 6 ...
Page 218: ...218 Notes ...
Page 219: ...219 Manuel d installation ...