www.kenall.com | P: 800-4-Kenall | F: 262-891-9701 | 10200 55th Street Kenosha, Wisconsin 53144, USA
This product complies with the Buy American Act: manufactured in the United State swith more than 50% of the component cost of US origin It may be covered by patents
found at www.kenall.com/patents. Content of specification sheets is subject to change; please consult www.kenall.com for current product details. ©2019 Kenall Mfg.Co.
6
INSTALLATION INSTRUCTIONS
F-2189
For warranty information visit www.kenall.com/Resources/Certified-Performance-Warranties
For technical assistance, call 1-800-4KENALL (1-800-453-6255).
WARRANTY
CUSTOMER SERVICE
120VAC Installation (Fig.1)
• Connect the WHITE wires from the BATTERY
HEATER to COMMON.
• Connect one RED wire from the THERMOSTAT
to the BLACK wire from the BATTERY HEATER.
• Connect the second RED wire from the
THERMOSTAT to 120VAC supply.
277VAC Installation (Fig.2)
• Connect one WHITE wire from the BATTERY
HEATER to COMMON.
• Cap off the BLACK wire from the
BATTERY HEATER.
• Connect one RED wire from the
THERMOSTAT to the second WHITE wire
from the BATTERY HEATER.
• Connect the second RED wire from the
THERMOSTAT to 277VAC supply.
Battery Maintenance (Fig.3)
• To remove battery, remove (2) screws
securing BATTERY RETAINER BRACKET.
Remove bracket.
• Unwrap the foil lined fiberglass INSULATION
from the BATTERY. There is no need to
remove the INSULATION.