KEOR COMPACT
DRY CONTACT CARD
10
3.7
Configure Output/Input Contacts
•
Please use the setting tool software to configure the output/Input contacts.
•
Go to
『
Setting
』
->
『
Configurations Value
』
->
『
Dry Contact
』
page to change the
definition for each contact.
•
Configure Output Relay
➢
The status and alarm events can be set.
➢
The status code list show as Table 2.
➢
The alarm code list show as Table 3.
➢
Example 1
:
Set Status S23
“Load on Bypass” to slot1 output relay1. Please keyin
setting value “1023”.
➢
Example 2
:
Set alarm A10 “Over Temperature” to slot2 output relay3. Please
keyin setting value “10”.
•
Configure Input Contact
➢
The available command code list show as Table 4.