KEOR COMPACT 

DRY CONTACT CARD 

 

 

1.  Introduction 

The  main  purpose  of  this  dry  contact  card  is  to  send  the  information  about  the  abnormal  events 
happen in UPS to the other apparatus so that this equipment can understand the current situation and 
act accordingly. This card provides six output relays and six input contacts. The UPS can install up to 2 
dry contact cards.  All output and input contacts are  programmable, and user can define the definition 
for each contact using setting tool. 
The prevalent requirements of output information include: Mains input fault alarm, Bypass fault alarm, 
Battery weak alarm, Output overload alarm so on and so forth.   
The  prevalent  requirement  of  input  information  includes:  Single  shutdown,  System  shutdown,  Single 
start,  System  start,  Transfer  to  bypass  in  single  operation,  Transfer  to  bypass  in  parallel  operation, 
EPO (Emergency shutdown). 
 
The purpose of this manual is to provide indications for installing and using safely the LEGRAND dry 
contact card 3 109 69. 
It is essential that this manual is read through, but it is not a substitute for the expertise of the technical 
personnel who must have had adequate preliminary training. 
The  dry  contact  card  has  been  built  for  the  applications  specified  in  this  manual.  For  no  reason 
whatsoever  it  is  allowed  a  use  for  purposes  other  than  those  for  which  it  has  been  designed,  nor  in 
ways different to those explained in the manual. 
 
This  manual  must be kept in  a safe, dry place and always  be available  for consultation.  We suggest 
making a copy and filing it.   
The manual is to be considered an integral part of the dry contact card and therefore must be kept for 
the card’s useful life cycle. 
The original text of this publication is in English and is the only reference for solving any interpretation 
disputes related to the translation into other languages. 
 
The  information  in  this manual  must  not  be disclosed to  third  parties. Any duplication, total  or partial, 
not authorized in writing by the Manufacturer violates the copyright conditions and can be prosecuted 
by law. 
LEGRAND reserves the property rights of this publication and forbids the total or partial reproduction of 
it without prior written consent. 
 

1.1 

Guarantee terms 

 
The  guarantee  conditions  may  vary  depending  on  the  country  where  the  dry  contact  card  is  sold. 
Check with your local LEGRAND sale representative for validity and duration. 
In order to use the guarantee supplied by the Manufacturer the user must scrupulously comply with the 
precautions indicated in the manual .   
The Manufacturer declines all liabilities, direct and indirect, resulting from:   

disregard  for  the  instructions  by  the  specialized  technician  and  a  use  of  the  card  different 
from the one stated in the manual; 

use by personnel who have not read and understood properly the contents of the manual; 

a use failing to conform to the specific laws existing in the country of installation;   

changes made to the equipment, operating logic or tampering; 

repairs unauthorized by the Technical Service Assistance of LEGRAND; 

damages  caused  by  willful  misconduct,  gross  negligence,  exceptional  events,  fire  or 
infiltration of liquids.   

 

 

Summary of Contents for KEOR COMPACT

Page 1: ...T 4 J5 NO NC OUT 5 J7 NO NC OUT 6 J8 1st 2nd J9 J3 1st 2nd J6 LE12723AA 20 12 The copying redistribution use or publication of such contents is strictly prohibited without Legrand authorization KEOR C...

Page 2: ...ty provisions 4 3 Installation Procedure 5 3 1 Component List 5 3 2 Electrical Specification 5 3 3 Dry Contact Card Hardware Setting 5 3 4 Pin Assignment of Output Input Contacts 7 3 5 Hardware Instal...

Page 3: ...e available for consultation We suggest making a copy and filing it The manual is to be considered an integral part of the dry contact card and therefore must be kept for the card s useful life cycle...

Page 4: ...lacement and guarantees Use only Legrand brand accessories DANGER The dry contact card must be installed only with the UPS UNPLUGGED FROM THE MAINS ATTENTION The dry contact card 3 110 99 can only be...

Page 5: ...ut Relay 250VAC 2A 30VDC 2A Input Contact When the contact is closed a current of 10mA max circulates 3 3 Dry Contact Card Hardware Setting Before installing this card to UPS please check below jumper...

Page 6: ...ot 2 1st 2nd J1 Out Relay 1 NO NC setting NO Normal Open NO NC J2 Out Relay 2 NO NC setting J4 Out Relay 3 NO NC setting J5 Out Relay 4 NO NC setting NC Normal Closed NO NC J7 Out Relay 5 NO NC settin...

Page 7: ...t as Figure 3 shows OUT IN IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 1 Output Relay 1 OUT 2 Output Relay 2 OUT 3 Output Relay 3 OUT 4 Output Relay 4 OUT 5 Output Relay 5 OU...

Page 8: ...y locked in to complete the installation procedure as Figure 4 shows Figure 4 3 6 Communication Setting Procedure Please configure the setting of this card via the LCD control panel and the setup proc...

Page 9: ...ease use the setting tool software to confirm the configuration of the dry contact card Go to Information Status Dry Contact page to identify whether the dry contact card is properly set If the card i...

Page 10: ...tion for each contact Configure Output Relay The status and alarm events can be set The status code list show as Table 2 The alarm code list show as Table 3 Example 1 Set Status S23 Load on Bypass to...

Page 11: ...KEOR COMPACT DRY CONTACT CARD 11 Example Set command C05 Shutdown to slot1 input contact 2 Please keyin setting value 5...

Page 12: ...Unitary Operation 1033 S34 Parallel Operation 1034 S35 Redundancy Operation 1035 S40 Vbatt Ok 1040 S41 Vbatt Low 1041 S42 Vbatt Min 1042 S48 Battery Charging Compensation 1048 S50 Battery Precharge K...

Page 13: ...hase Current Unbalance 49 A50 Mains Input Voltage Low 50 A58 Inverter Output Voltage out of Tolerance 58 A59 Output contactor broken or output fuse open 59 A60 Inverter Output DC Offset too High 60 A6...

Page 14: ...e List Code Description Setting Value C00 Normal Mode 0 C02 ECO Mode 2 C03 Converter Mode 3 C05 Shutdown 5 C06 Load on Bypass 6 C11 Buzzer Disable 11 C12 Buzzer Enable 12 C14 Clear Latch Alarm and Buz...

Page 15: ...KEOR COMPACT DRY CONTACT CARD 15...

Page 16: ...KEOR COMPACT DRY CONTACT CARD 16...

Reviews: