KEOR COMPACT
DRY CONTACT CARD
6
Table 1
Jumper
Function Descriptions
Setting
J3
J6
J9
These three jumpers to select the
communication slot of UPS which one
this dry-contact card will be installed.
Slot 1:
1st 2nd
Slot 2:
1st 2nd
※
J1
Out Relay#1 NO/NC setting
NO (Normal Open)
NO NC
J2
Out Relay#2 NO/NC setting
J4
Out Relay#3 NO/NC setting
J5
Out Relay#4 NO/NC setting
NC (Normal Closed)
NO NC
J7
Out Relay#5 NO/NC setting
J8
Out Relay#6 NO/NC setting
※
Check the TACI4xx PCB board SW2 is on the Slot sides Figure 2 shows
Figure 2. TACI4XX PCB board SW2
If you insert Dry Contact Card into the Slot2
,
you must select Slot side on the SW2.