KEOR COMPACT
DRY CONTACT CARD
8
3.5
Hardware Installation Procedure
Please refer to section 1.3 to set all jumpers of the dry contact card before install to UPS.
Plug in the dry contact card to the
《
Slot1
》
or
《
Slot2
》
and then screw in the screws after the card is
firmly locked in to complete the installation procedure, as Figure 4 shows.
Figure 4
3.6
Communication Setting Procedure
•
Please configure the setting of this card via the LCD control panel and the setup procedure
as shows in Figure 5.
•
The programmable parameters as shows in table below.
Item
Setting
ID
1
Stop Bit
1
Parity Check
None
Baud Rate
57600
•
In parallel system, please click
to select the machine ID which installs the dry contact
card before you change the setting.