background image

KEOR COMPACT 

DRY CONTACT CARD 

 

 

3.5 

Hardware Installation Procedure 

Please refer to section 1.3 to set all jumpers of the dry contact card before install to UPS. 

Plug in the dry contact card to the

Slot1

or

Slot2

and then screw in the screws after the card is 

firmly locked in to complete the installation procedure, as Figure 4 shows. 
 

 

Figure 4 

 
 

3.6 

Communication Setting Procedure 

 

Please configure the setting of this card via the LCD control panel and the setup procedure 
as shows in Figure 5. 

 

The programmable parameters as shows in table below. 

Item 

Setting 

ID 

Stop Bit 

Parity Check 

None 

Baud Rate 

57600 

 

In parallel system, please click 

  to select the machine ID which installs the dry contact 

card before you change the setting. 

 
 

 

Summary of Contents for KEOR COMPACT

Page 1: ...T 4 J5 NO NC OUT 5 J7 NO NC OUT 6 J8 1st 2nd J9 J3 1st 2nd J6 LE12723AA 20 12 The copying redistribution use or publication of such contents is strictly prohibited without Legrand authorization KEOR C...

Page 2: ...ty provisions 4 3 Installation Procedure 5 3 1 Component List 5 3 2 Electrical Specification 5 3 3 Dry Contact Card Hardware Setting 5 3 4 Pin Assignment of Output Input Contacts 7 3 5 Hardware Instal...

Page 3: ...e available for consultation We suggest making a copy and filing it The manual is to be considered an integral part of the dry contact card and therefore must be kept for the card s useful life cycle...

Page 4: ...lacement and guarantees Use only Legrand brand accessories DANGER The dry contact card must be installed only with the UPS UNPLUGGED FROM THE MAINS ATTENTION The dry contact card 3 110 99 can only be...

Page 5: ...ut Relay 250VAC 2A 30VDC 2A Input Contact When the contact is closed a current of 10mA max circulates 3 3 Dry Contact Card Hardware Setting Before installing this card to UPS please check below jumper...

Page 6: ...ot 2 1st 2nd J1 Out Relay 1 NO NC setting NO Normal Open NO NC J2 Out Relay 2 NO NC setting J4 Out Relay 3 NO NC setting J5 Out Relay 4 NO NC setting NC Normal Closed NO NC J7 Out Relay 5 NO NC settin...

Page 7: ...t as Figure 3 shows OUT IN IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 1 Output Relay 1 OUT 2 Output Relay 2 OUT 3 Output Relay 3 OUT 4 Output Relay 4 OUT 5 Output Relay 5 OU...

Page 8: ...y locked in to complete the installation procedure as Figure 4 shows Figure 4 3 6 Communication Setting Procedure Please configure the setting of this card via the LCD control panel and the setup proc...

Page 9: ...ease use the setting tool software to confirm the configuration of the dry contact card Go to Information Status Dry Contact page to identify whether the dry contact card is properly set If the card i...

Page 10: ...tion for each contact Configure Output Relay The status and alarm events can be set The status code list show as Table 2 The alarm code list show as Table 3 Example 1 Set Status S23 Load on Bypass to...

Page 11: ...KEOR COMPACT DRY CONTACT CARD 11 Example Set command C05 Shutdown to slot1 input contact 2 Please keyin setting value 5...

Page 12: ...Unitary Operation 1033 S34 Parallel Operation 1034 S35 Redundancy Operation 1035 S40 Vbatt Ok 1040 S41 Vbatt Low 1041 S42 Vbatt Min 1042 S48 Battery Charging Compensation 1048 S50 Battery Precharge K...

Page 13: ...hase Current Unbalance 49 A50 Mains Input Voltage Low 50 A58 Inverter Output Voltage out of Tolerance 58 A59 Output contactor broken or output fuse open 59 A60 Inverter Output DC Offset too High 60 A6...

Page 14: ...e List Code Description Setting Value C00 Normal Mode 0 C02 ECO Mode 2 C03 Converter Mode 3 C05 Shutdown 5 C06 Load on Bypass 6 C11 Buzzer Disable 11 C12 Buzzer Enable 12 C14 Clear Latch Alarm and Buz...

Page 15: ...KEOR COMPACT DRY CONTACT CARD 15...

Page 16: ...KEOR COMPACT DRY CONTACT CARD 16...

Reviews: