6.7 BATTERY
TEST
The BATTERY TEST menu allows to carry out a short discharge test of the battery. In case
the battery is not efficient, the alarm “A10 – Battery fault” is generated at the end of the test.
BATTERY TEST?
The value on the second line is ready to be
changed
NO
(1x)
BATTERY TEST?
The parameter is changed. The change is
confirmed by pressing
(ENTER)
YES
SPECIAL
The system performs a reset and returns to the
previous screen
BAT
TERY TEST
Possible loss of supply
This test can affect the continuity of supply to the loads if the battery is not fully
charged.
6.8 SYSTEM
RESET
The UPS is equipped with internal protections which block the system or some of its
sections. The alarm can be cleared and normal operation can be resumed via the RESET
menu. In case the failure persists, the UPS will return to the previous failure condition.
In some cases the RESET is necessary to simply reset a failure signal, then the UPS will
resume operation.
RESET DEVICE?
The value on the second line is ready to be
changed
NO
(1x)
RESET DEVICE?
The parameter is changed. The change is
confirmed by pressing
(ENTER)
YES
SPECIAL
The system performs a reset and returns to the
previous screen
RESET
Summary of Contents for KEOR HP 100kVA
Page 55: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 55 FRANÇAIS ...
Page 85: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 85 ...
Page 87: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 87 ...
Page 136: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS 136 OMD10074 REV C ...