3.3.3 Minimum distances from the walls and ventilation
The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as
much as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same
installation conditions apply as indicated in the table below.
Picture 5 – Minimum distances from the walls
A (mm)
B (mm)
D (mm)
1000 700 50
The table below shows the air volume required for an optimal ventilation and cooling of the
UPS.
Power (kVA)
200 250 300
Air volume (m
3
/h) 3500
4100
4500