5. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
6. Follow the procedure shown at paragraph 4.4 to insert a new battery drawer
INDICATION
If the UPS turns to battery mode during these operations, do not continue the installation/replacement. It is possible to
resume the operations when the UPS turns to on-line mode.
When there is a black-out during the replacement of battery drawers, the backup time is reduced. It is necessary to care-
fully assess this event before starting with the installation/replacement procedure.
To add a battery drawer:
Follow the procedure shown at paragraph 4.4 to add a new battery drawer
6.4.2 Installation/replacement of battery drawers with UPS in maintenance manual bypass
To replace a battery drawer:
1. Follow the procedure described in paragraph 6.3.2.1 for setting the UPS in maintenance bypass mode.
2. Extract the battery drawer until the safety block prevents to continue the extraction.
Summary of Contents for Keor MOD 100
Page 1: ...Part LE11406AB 04 19 01 GF Keor MOD Installation and maintenance manual ...
Page 2: ...2 EN ENGLISH 3 Keor MOD ...
Page 20: ...20 4 Installation 3 4 5 ...
Page 22: ...22 4 Installation 9 10 ...
Page 24: ...24 4 Installation KEOR MOD 250 earthing bars ...
Page 79: ...Keor MOD Installation and maintenance manual 79 6 3 3 Removal of the SSS drawer 1 2 3 4 ...
Page 87: ...Keor MOD Installation and maintenance manual 87 ...
Page 88: ...88 9 Mechanical characteristics ...
Page 89: ...Keor MOD Installation and maintenance manual 89 ...
Page 90: ...90 9 Mechanical characteristics ...
Page 92: ...92 9 Mechanical characteristics 9 3 Battery drawer all the dimensions are in mm ...