94
10. Technical data
Main features
Keor
MOD
25
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
Keor
MOD
125
Keor
MOD
150
Keor
MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
Nominal Power
(kVA)
25
50
75
100
125
150
175
200
225
250
Active Power
(kW)
25
50
75
100
125
150
175
200
225
250
Number of power
modules
1
2
3
4
5
6
7
8
9
10
Technology
online, double conversion
VFI-SS-111 (EN62040-3)
IN/OUT configuration
Three-phase / Three-phase
Dual Input
Available
UPS system
Modular, expandable and redundant
Neutral system
Neutral passing straight from input to output (not isolated)
Bypass
Automatic (static and electromechanical)
Manual (for maintenance)
Overvoltage category
OVC II
Input electrical characteristics
Keor
MOD
25
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
Keor
MOD
125
Keor
MOD
150
Keor
MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
Rated input current (A)
(full load and 400V
input voltage)
37.6
75
113
150
188
225.6
263.2
300
338
376
Maximum input
current (A)
(full load and 320V
input voltage)
47
94
141
188
235
282
329
376
423
470
Input voltage
(V)
400 + 15% - 20%
(3F+N+PE)
Input frequency
(Hz)
50 / 60 ± 2%
50 / 60 ± 14 %
(autosensing and/or selectable by the user)
Input Power Factor
> 0.99
Total harmonic distortion
of the input current
THDi < 3% (at full load)
Icp
Prospective short-circuit
current (kA)
10
Summary of Contents for Keor MOD 100
Page 1: ...Part LE11406AB 04 19 01 GF Keor MOD Installation and maintenance manual ...
Page 2: ...2 EN ENGLISH 3 Keor MOD ...
Page 20: ...20 4 Installation 3 4 5 ...
Page 22: ...22 4 Installation 9 10 ...
Page 24: ...24 4 Installation KEOR MOD 250 earthing bars ...
Page 79: ...Keor MOD Installation and maintenance manual 79 6 3 3 Removal of the SSS drawer 1 2 3 4 ...
Page 87: ...Keor MOD Installation and maintenance manual 87 ...
Page 88: ...88 9 Mechanical characteristics ...
Page 89: ...Keor MOD Installation and maintenance manual 89 ...
Page 90: ...90 9 Mechanical characteristics ...
Page 92: ...92 9 Mechanical characteristics 9 3 Battery drawer all the dimensions are in mm ...