98
11. Tables
CAUTION
The choice of the type and section of the power cables must be done according to the voltage and rated current as well
as the local wiring standards and regulations. It is a responsibility of the installation engineer.
The input current and the output power of the UPS are indicated in chapter 10 and the battery current in table 4 of this chapter.
The following tables give an indication of the wire cross sections to use if the wires are unipolar with simple PVC installa-
tion and installation in tube in the air.
TABLE 1
Minimum wire cross sections recommended for Keor MOD UPS
POWER
INPUT CABLE
BYPASS CABLE
(in case of separate
bypass line)
OUTPUT CABLE
125 kVA
Phase: 1 x 95 mm
2
or 2 x 50 mm
2
per pole
Neutral: 1 x 120 mm
2
or 2 x 70 mm
2
Phase: 1 x 95 mm
2
or 2 x 50 mm
2
per pole
Neutral: 1 x 120 mm
2
or 2 x 70 mm
2
Phase: 1 x 95 mm
2
or 2 x 50 mm
2
per pole
Neutral: 1 x 120 mm
2
or 2 x 70 mm
2
250 kVA
Phase: 1 x 185 mm
2
or 2 x 95 mm
2
per pole
Neutral: 1 x 240 mm
2
or 2 x 120 mm
2
Phase: 1 x 185 mm
2
or 2 x 95 mm
2
per pole
Neutral: 1 x 240 mm
2
or 2 x 120 mm
2
Phase: 1 x 150 mm
2
or 2 x 70 mm
2
per pole
Neutral: 1 x 240 mm
2
or 2 x 120 mm
2
TABLE 2
Automatic breaker recommended for input and bypass line
POWER
AUTOMATIC CIRCUIT BREAKER
125 kVA
In=250 A curve C Icp=10kA
250 kVA
In=630 A curve C Icp=10kA
TABLE 3
Residual current breaker recommended for input and bypass line
POWER
RESIDUAL CURRENT BREAKER (IΔn)
125 kVA
≥ 300 mA type B
250 kVA
Summary of Contents for Keor MOD 100
Page 1: ...Part LE11406AB 04 19 01 GF Keor MOD Installation and maintenance manual ...
Page 2: ...2 EN ENGLISH 3 Keor MOD ...
Page 20: ...20 4 Installation 3 4 5 ...
Page 22: ...22 4 Installation 9 10 ...
Page 24: ...24 4 Installation KEOR MOD 250 earthing bars ...
Page 79: ...Keor MOD Installation and maintenance manual 79 6 3 3 Removal of the SSS drawer 1 2 3 4 ...
Page 87: ...Keor MOD Installation and maintenance manual 87 ...
Page 88: ...88 9 Mechanical characteristics ...
Page 89: ...Keor MOD Installation and maintenance manual 89 ...
Page 90: ...90 9 Mechanical characteristics ...
Page 92: ...92 9 Mechanical characteristics 9 3 Battery drawer all the dimensions are in mm ...