31
KEOR T
Oper
ating M
anual
* Keor T 60kVA battery fuses are fixed.
7. Operating Procedures For Single Systems
7.1.
Preparations
UPS is shipped with 3pcs of battery fast fuses in a plastic package attached to the front side of UPS.
After all connections are completed as described in Keor T Installation Manual, the battery fuses must be placed
as shown below. The fuses’ indicators should be placed at top. Use only the fuses delivered with the UPS.
Figure.7.1-1
Figure.7.1-2
KEOR T 5-30KVA
KEOR T 40-50KVA
INDICATORS
Summary of Contents for Keor T 10KVA
Page 1: ...LE10795AB KEOR T 208V 5 60 KVA Operating Manual ...
Page 4: ...KEOR T ...
Page 53: ...49 KEOR T Operating Manual SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Page 54: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...
Page 55: ...51 KEOR T Operating Manual COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Page 56: ...52 COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...