Important Notices!
Thank you for choosing LEGRAND UPS System to supply your Critical Application.
This manual contains important information about commissioning, usage and technical properties of the
UPS. It also contains safety information for operator and instructions to secure your critical load. Applying
the recommendation detailed in this manual is necessary to use UPS safely and correctly.
The manufacturer reserves the rights to change the t
echnical specifica
tions
and design without notice.
LEGRAND reserves the rights to change the information in this document
without notice. Refer to
http://ups.legrand.com/
web site to dowload last
release and translations.
Units that are labelled with a CE mark comply with the Standard: EN 62040-1 and EN 62040-2.
Read the manual completely before working on this equipment!
Keep this manual in UPS’s front cover’s pocket for easy consultation!
Reproduction, adaptation, or translation of this manual is prohibited without prior
written permission of LEGRAND Company, except as allowed under the copyright laws.
7
8
76
Appendix-4: Technical Sp
ecific
ations
Tower Model (3Ph/3Ph)
KEOR T EVO
10KVA
KEOR T EVO
15KVA
KEOR T EVO
20KVA
KEOR T EVO
30KVA
KEOR T EVO
40KVA
KEOR T EVO
60KVA
Output Power (VA)
10.000
15.000
20.000
30.000
40.000
60.000
Nominal Active Power (W)
10.000
15.000
20.000
30.000
40.000
60.000
Rec
tifier I
nput
Nominal Voltage
400V (Ph-Ph) 3Ph+N+PE
Input Voltage Range (VAC) (at 50% Load)
242-459V
Input Voltage Range (VAC) (at full Load, with battery
charging)
±15%
Frequency (Hz)
45 - 65
Power Factor
≥ 0.99
Bypass Input
Nominal Voltage
400V (Ph-Ph) 3Ph+N+PB
Voltage Tolerance
±18% (Customizable)
Frequency Tolerance (Hz)
±3
Transfer Time (ms)
<1
Output
Nominal Voltage (VAC) (Ph-Ph)
400V (Ph-Ph) 3Ph+N+PB (380/415 Adjustable)
Power Factor
1.0
Wave Form
Sinusoidal
Frequency (Hz)
50 or 60 (Adjustable)
Frequency Tolerance (Battery Operation)
0.01%
Voltage Regulation (Static)
±1%
Output voltage unbalance at reference unbalance
load
<0.5%
Maximum phase angle variation
<0.1°
Crest Factor
3:1
Nominal Power (kVA)
10
15
20
30
40
60
Overload Protection (sec)
600 (at 100 - 125% Load)
60 (at 125 - 150% Load)
THD
V
< 2%
Non-Linear Load < 4%
Battery
Battery Type
Maintenance-Free Lead Acid Batteries
Battery String (Blocks)
1x60
Protection
Overload Protection, High Temperature, Input Over Voltage, Input & Output Over Current,
Intelligent Charging Algorithm - Deep Charge Protection - Battery Test (Automatic /
Manual), Short-Circuit Protection
Standard Protection