While reading data through MODBUS, the following addresses can be used. “03 - Read Holding Registers”
must be selected to read the MODBUS data.
We can send commands by using MODBUS. To do that function 06 – Write Single Register must be used.
The data is defined as unsigned words (2 bytes).
Appendix-5: Modbus List
Address
Coefficient
Data Definition
Read (R) / Write (W)
100
1
L1 Input Voltage
R
101
1
L2 Input Voltage
R
102
1
L3 Input Voltage
R
103
1
L1 Input Current
R
104
1
L2 Input Current
R
105
1
L3 Input Current
R
106
0,1
Input Frequency
R
107
1
L1 Output Voltage
R
108
1
L2 Output Voltage
R
109
1
L3 Output Voltage
R
110
1
L1 Output Current
R
111
1
L2 Output Current
R
112
1
L3 Output Current
R
113
0,1
Output Frequency
R
114
1
L1 Output Load Percentage
R
115
1
L2 Output Load Percentage
R
116
1
L3 Output Load Percentage
R
117
1
L1 Bypass Voltage
R
118
1
L2 Bypass Voltage
R
119
1
L3 Bypass Voltage
R
120
1
Positive Battery String Voltage
R
121
1
Negative Battery String Voltage
R
122
1
Positive Battery String Current
R
123
1
Negative Battery String Current
R
124
1
Battery / Ambient Temperature
R
125
1
Positive DC Bus String Voltage
R
126
1
Negative DC Bus String Voltage
R
127
1
UPS Conditions and Alarms (***)
R
201
1
If “1” is sent then beeper will be on. If “0” is sent then beeper will be off.
R/W
202
1
If “1” is sent then a battery test will start.
R/W
Summary of Contents for KEOR T EVO
Page 1: ...KEOR T EVO 10 15 20 KVA Installation Operation Manual LE10507AA ...
Page 2: ...LE10507AA KEOR T EVO ...
Page 24: ...22 Figure 6 3 1 3 Figure 6 3 1 4 Power Cables Path Communication Cables Path ...
Page 30: ...28 Figure 6 3 1 4 1 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 32: ...30 Figure 6 3 1 4 3 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 76: ...74 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT ...
Page 82: ...Notes ...
Page 83: ......