16
Installation Parameters
Model (kVA)
10
15
20
30
40
60
Phase in/out
3Ph+N/3Ph+N
Rated output apparent power (kVA)
10
15
20
30
40
60
Rated output active power (kW)
9
13,5
18
27
36
54
Rated input current (A) at 400V nominal input voltage
14
21
28
42
57
84
Maximum input current (A) at 340V input v full load + battery charging
18
27
36
54
72
105
Rated bypass current (A) at 400V nominal input voltage
15
22
29
44
58
87
Maximum bypass current (A) at 400V, 125% overload 10 min
19
28
36
55
73
109
Inverter output current @ 400V (A)
15
22
29
44
58
87
Maximum Inverter output current (A) at 400V, 125% overload 10 min
19
28
36
55
73
109
Overload tolerated by the inverter (with mains power present) (kW)
10
min
11,3
16,9
22,5
33,8
45
67,5
1 min
13,5
20,3
27
40,5
54
81
Recommended Protection Devices - Rectifier/Mains Supply -*
D curve circuit breaker (A) (3-pole)
20
25
40
50
63
100
GG fuse (A)
20
25
40
50
63
100
Recommended Protection Devices – General Bypass/Auxiliary Mains Supply –*
D curve circuit breaker (A) (3-pole)
20
25
40
50
63
100
Maximum I2t supported by the bypass (A2s)
6700
11200
15000
25300
Icc max (A)
1200
1500
1700
2300
Protection Devices – Battery Fast Fuse –
Ferrule style high speed fuses and with indicating striker
(High Speed FWP Bussmann Fuse 22x58mm 690VAC (IEC)) (A)
25
32
50
63
80
100
Recommended Protection Devices – Output –
C curve circuit breaker (A) (3-pole) **
≤3
≤4
≤4
≤6
≤10
≤13
B curve circuit breaker (A) (3-pole) **
≤6
≤8
≤8
≤13
≤20
≤25
Maximum interter I2t at 100ms (A2s)
66
150
130
480
900
1900
Max. Cable Cross-Section for Terminals***
Rectifier (mm²)
35
General Bypass (mm²)
35
Battery (mm²)
16
35
Output (mm²)
35
Neutral (mm²)
35 (Battery Neutral: 16)
35
Protective Earth/Bonding
Recommended cross section for ground wire
at least half of the section of cable phases AND
shall comply with the standards of the country
(for example NFC 15100 in France).
Leakage Current Protection ****
Minimum 300 mA delayed (Type-B). When used,
the residual current earth leakage protection
system must be common for the two AC inputs
(common & auxiliary mains) and installed
upstream.
Table.2
Summary of Contents for KEOR T
Page 1: ...KEOR T Installation Manual LE07544AA ...
Page 2: ...2 KEOR T ENGLISH 6 EN ...
Page 5: ...5 KEOR T Installation Manual Battery Fast Fuses Installation Operating Manuals ...
Page 32: ...32 Figure 5 3 1 4 1 Keor T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Page 34: ...34 Figure 5 3 1 4 3 Keor T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Page 50: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS ...
Page 51: ...51 KEOR T Installation Manual COMMON RECTIFIER AND BYPASS INPUTS ...