Catalogue number(s): 0 463 00/06/12/18/19/21/22/23
0 463 28/29/30/33/34/35/41/42/43
19" LCS
2
freestanding cabinets
Technical data sheet: F01424EN/01
Updated on: 24/10/2014
Created on: 21/02/2012
28/31
12. POWER DISTRIBUTION
(continued)
12.1 Vertical PDUs
(continued)
12.1.1 Single phase PDU
PDUs comprising 2 circuits.The total number of sockets is distributed
equally between the 2 circuits.
Each circuit is identified by colour coding (white sockets and black
sockets).
Cat. No.
2P+E sockets
Connection
Number
Standard
0 465 81
24
C13 IEC 60320
4/6 mm
2
terminal block
via cable gland
(1)
0 465 84
16
C13 IEC 60320
3x2.5 mm
2
cord of 3 m
lenght with IEC 60309
2P+E plug 32A
6
C19 IEC 60320
0 465 80
24
French - Belgian
4/6 mm
2
terminal block
via cable gland
(1)
0 465 88
24
German
0 465 89
22
British
(1)
Clamping capacity: Ø12 to Ø18 mm
Features
Cat. No.
Power supply
Use
Voltage
Max. current
Power
(1)
Protection
(1)
0 465 81
230V - 250V
50/60 Hz
16A
3680 W
16A circuit
breaker
Single pole
+ neutral
C type
0 465 84
0 465 80
0 465 88
16A circuit
breaker
Single pole
C type
0 465 89
(1)
Per circuit
12.1.2 Three-phase PDU
One circuit per phase composed of 8 C13 s 1 C19 socket.
Cat. No.
2P+E sockets
Connection
Number
Standard
0 465 85
24
C13 IEC 60320
5x4 mm
2
cord of 3 m lenght
with IEC 60309 3P+N+E
plug 32A
3
C19 IEC 60320
Features
Cat. No.
Power supply
Use
Voltage
Max. current
Power
(1)
Protection
(1)
0 465 85
380V
50/60 Hz
32A
3680 W
16A circuit
breaker
Single pole
+ neutral
C type
(1)
Per circuit/phase
12. POWER DISTRIBUTION
(continued)
12.1 Vertical PDUs
(continued)
0 465 80 0 465 81
0 465 85
0 465 88
0 465 84
0 465 89
Legrand also has a range of 19" PDU and vertical PDU with
intensity measure ability. To know all the features of these metered
PDU, consult the specific data sheet.