Line Interactive UPS User Manual
Specifications
46
©2022 |
. All rights reserved.
Expandable Runtime Battery Option (ERB)
Model
UPX-1000R-2
UPX-RLNK-1000R-2
UPX-RLNK-1000R-8
UPX-1500R-2
UPX-RLNK-1500R-2
UPX-RLNK-1500R-8
UPX-2000R-2
UPX-RLNK-2000R-2
UPX-RLNK-2000R-8
Composition
Lead Acid
Recharge Time
6 – 8 hours
Battery Replacement
Hot Swappable Front Access
Replacement Battery
Part Numbers
UPX-RPLBATT-A
(ERB requires two batteries.)
UPX-RPLBATT-D
(ERB requires two
batteries.)
UPS + 1 ERB
Full- and Half-Load Runtimes
23 | 55 minutes
12 | 37 minutes
17 | 42 minutes
UPS + 2 ERB
Full- and Half-Load Runtimes
43 | 105 minutes
28 | 74 minutes
33 | 83 minutes
UPS + 3 ERB
Full- and Half-Load Runtimes
68 | 164 minutes
43 | 111 minutes
50 | 135 minutes
UPS + 4 ERB
Full- and Half-Load Runtimes
93 | 222 minutes
60 | 154 minutes
71 | 178 minutes
Environment
Model
UPX-1000R-2
UPX-RLNK-1000R-2
UPX-RLNK-1000R-8
UPX-1500R-2
UPX-RLNK-1500R-2
UPX-RLNK-1500R-8
UPX-2000R-2
UPX-RLNK-2000R-2
UPX-RLNK-2000R-8
Operating Temperature
and Relative Humidity
32
⁰
F (
0⁰
C) – 104
⁰
F (40
⁰
C)
0% – 95% Non-Condensing
Storage Temperature
5
⁰
F (-15
⁰
C) – 113
⁰
F (45
⁰
C)
Communication
Model
UPX-1000R-2
UPX-RLNK-1000R-2
UPX-RLNK-1000R-8
UPX-1500R-2
UPX-RLNK-1500R-2
UPX-RLNK-1500R-8
UPX-2000R-2
UPX-RLNK-2000R-2
UPX-RLNK-2000R-8
NEXSYS UPS Manager
Software
Supports Windows® 7, 8, 10, and 11 and Windows Server 2008, 2012, 2016, and 2019,
Windows 2008, 2012 Server Core, and Hyper-V 2008, 2012