21
8. SPECIFICATIONS
8-1. UPS without ISO transformer
3000 VA/2400 W
3 kVA
72 FM
MODEL
CAPACITY*
Voltage
Low line transfer
Low line comeback
High line transfer
High line comeback
1 kVA
FM
Frequency range
Phase
Power factor
Output voltage
AC voltage regulation
Frequency Range
(Synchronized Range )
Frequency Range
(Batt. Mode)
Overload
Current crest ratio
Harmonic distortion
Transfer
time
Waveform (Batt. mode)
AC mode to Batt. mode
Inverter to Bypass
160 VAC/140 VAC/120 VAC/110 VAC ± 5%
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
185 VAC/165 VAC/145 VAC/135 VAC ± 5 %
(based on load percentage 100% - 80%/80% - 70%/70 - 60%/60% - 0)
300 Vac ± 5%
290 Vac ± 5%
40 Hz ~ 70 Hz
Single phase with ground
≥ 0.99
@
nominal input voltage
200/208/220/230/240 Vac
± 1%
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
105%~110%:
UPS shuts down after 10 min at battery mode
or transfer to Bypass when the utility is normal
110%~130%:
UPS shuts down after 1 min at battery mode
or transfer to Bypass when the utility is normal
>130%:
UPS shuts down after 3 secs at battery mode
or transfer to Bypass when the utility is normal
3:1
≤
3% THD (Linear load)
≤
5% THD (Non-linear load)
Zero
4 ms (Typical)
Pure Sinewave
2000 VA/1600 W
1000 VA/800 W
2 kVA
72 FM
2 kVA
96 FM
3 kVA
96 FM
INPUT
OUTPUT
22
Battery type
Battery numbers
Maximum battery AH
Current of external
Batt.
pack
Charging current
Charging voltage
Depending on the capacity of external batteries
EXTERNAL BATTERY
ENVIRONMENT
Supports Windows
®
2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Power management from SNMP manager and web browser
MANAGEMENT
Operation humidity
Noise level
20-90% RH
@
0- 40°C (non-condensing)
Less than 50 dBA
@
1 Meter (AVG)
Smart RS-232 or USB
Optional SNMP
3
150
30 A max
1.0A/2.0A/
4.0A/8.0A
41.0 Vdc ± 1%
6
200
30 A max
82.1 Vdc ±1%
8
200
30 A max
109.5 Vdc ±1%
6
200
45 A max
82.1 Vdc ±1%
8
200
32 A max
109.5 Vdc ±1%
Dimension (D x W x H) mm 405x145x235
435 x 190 x 335
Net weight (kgs)
6.2
11.5
12.0
PHYSICAL
1.0A/2.0A/4.0A/6.0 A
*Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted
to 208 VAC/200 VAC. Product specifications are subject to change without further notice.