41
5.2 Main page
After powering on, it will enter system monitor main page, as shown in Figure 5-2.
After entering the mains page, user can monitor the system conveniently. The meaning of icon in main page is
as follows:
: System bypass input. When bypass input is abnormal, the icon flickers and shows as
: System mains input. When mains input is abnormal, the icon flickers and shows as
: Battery status. When battery is abnormal, the icon flickers and shows as
: System output. When output is abnormal, the icon flickers and shows as
: Back to home page
: Information records
: System parameter setting
: Login
: Buzzer
: Warning
: ON/OFF
The work status and energy flow on main page shows the system running status and unit running
condition directly.
5 TOUCH SCREEN OPERATION AND SETTING
This section mainly introduces the work parameters and work status and system setting of the UPS.
5.1 Menu hierarchy
Figure 5-1. Menu structure
Note:
40 kVA series UPS adopt 4.3” touch screen to display. In this
section, we take 4.3” touch screen for illustration.
Figure 5-2. Main page
Voltage/ current/ frequency
Voltage/ current/ active power/ apparent power/ frequency
Voltage/ charge current/ discharge current/ temperature/ backup time/ capacity/ status
Voltage/ current/ active power/ apparent power/ load rate/ frequency
Input voltage & frequency/ output voltage & frequency/ output frequency
tracking range/ tracking rate/ adjust output voltage
Manual mode setting/ timing mode setting/ timing ON setting/ timing OFF
setting/ timing repeat
Standard test/ depth test/ cancel test
Generator control/ generator starting mode/ generator charging output/
charger power setting/ generator battery low-voltage start point
Timing self-dedusting/ regular dedusting period/ forced dedusting
Date & time/ backlight time/ brightness adjust
Device S/N, product name, model, software version,
hardware version, screen version, device status
Manufacturer, producing area, postcode, service tel
Battery equalized charge voltage/battery float charge voltage/ charge currentlimit
coefficient/ battery equalized charge current/ equalized charge last time/
enable timing equalized charge/ timing equalized charge interval/ equalized
charge protection interval/ forced equalized charge/ forced float charge/
enable temperature compensation/ temperature compensation coefficient
Max. & min. bypass voltage/ bypass frequency range/ ECO voltage &
frequency range/ inverter and bypass out-sync alarm/ max. switch time from
inverter mode to bypass mode when unsync/ max. switch time from bypass
mode to inverter mode when unsync
Battery capacity/ battery amount/ shared battery in parallel system/ battery
backup time alarm/battery over-voltage protection point/ battery under-voltage
protection point/ battery secondary under-voltage protection point/ battery
secondary under-voltage protection/ auto start when power recovers after
under-voltage protection/ battery circuit abnormal alarm/ battery lowtemperature
alarm point/ battery high-temperature alarm point/ battery
discharge time limit/ battery discharge protection time
Mains
Bypass
Battery
Output
System setting
Bypass System
Battery manage
Battery test
Main page
System manage
Function setting
HMI setting
Password setting
History fault
User log
Product info.
Manufacturer info.
Monitor page
System
setting
Information
ON/OFF
ECO setting
ECO setting
ECO setting
ECO setting
ECO setting
REC.
BYPASS
MAINS
BATT.
INV.
OUTPUT
Output:
Initializing
2017.12.12 20:06:12
P-U(V) P-V(V)
P-W(V)
Freq.(Hz)
0.0
0.0
0.00
0.0