background image

COVERAGE PATTERNS

The OS300S will cover up to 300 sq. ft. The typical recommended coverage for
desktop activity is 150 sq. ft. The sensor has a two-tiered, multi-cell viewing
Fresnel lens with 180 degree field of view.

4.0'

(1.2m)

25'

(7.6m)

floor

Masking the lens

Opaque adhesive tape is supplied so that sections of the sensor’s view can
be masked. This allows you to eliminate coverage in unwanted areas. Since
masking removes bands of coverage, remember to take this into account when
troubleshooting coverage problems.

25'

(7.6m)

10'

(3.1m)

Summary of Contents for Pass & Seymour OS300S

Page 1: ...its 120VAC 0 800W tungsten or ballast 277VAC 0 1200W ballast Load Type Compatibility incandescent fluorescent magnetic or electronic ballast Time Delay Adjustment 5 to 30 minutes user selectable or au...

Page 2: ...elay period There is a 30 second reset delay If motion is detected during this time the sensor will turn the lights back ON automatically After the reset delay time has elapsed the Auto ON OFF button...

Page 3: ...tomatically adjusts to avoid common ambient conditions that can cause false detections while providing maximum coverage Light Level Control Lights are held OFF even when the controlled area is Enabled...

Page 4: ...To verify proper operation place the unit in any Fixed time delay any of switches 1 2 or 3 in the ON position then select Automatic time delay switches 1 2 and 3 in the OFF position to temporarily re...

Page 5: ...viewing Fresnel lens with 180 degree field of view 4 0 1 2m 25 7 6m floor Masking the lens Opaque adhesive tape is supplied so that sections of the sensor s view can be masked This allows you to elimi...

Page 6: ...e wall box by inserting screws into the two wide holes on the top and bottom of the attached metal bracket Match them up with the holes in the wall box and tighten 4 Turn circuit breaker ON Wait one m...

Page 7: ...nto the unit Reinstall the cover plate Light Level Adjustment To set or reset the threshold to match a current ambient light level put the sensor into TEST mode Press and hold the button for 3 seconds...