Ju
ne
20
18
214 Legrand PDU User Guide
Sample Event Rules
Sample PDU-Level Event Rule
In this example, we want the Legrand PDU to record the firmware upgrade failure in the internal log when it
happens.
The event rule involves:
Event: Device > Firmware update failed
Action: System Event Log Action
To create this PDU-level event rule:
1. For an event at the PDU level, select "Device" in the Event field.
2. Select "Firmware update failed" so that the Legrand PDU responds to the event related to firmware
upgrade failure.
3. To make the Legrand PDU record the firmware update failure event in the internal log, select "System
Event Log Action" in the Available Actions field.
Sample Outlet-Level Event Rule
In this example, we want the Legrand PDU to send SNMP notifications to the SNMP manager for any sensor
change event of outlet 3.
The event rule involves:
Event: Outlet > Outlet 3 > Sensor > Any sub-event
Action: System SNMP Notification Action
To create this outlet-level event rule:
1. For an event at the outlet level, select "Outlet" in the Event field.
2. Select "Outlet 3" because that is the desired outlet.
3. Select "Sensor" to refer to sensor-related events.
4. Select "Any sub-event" to include all events related to all sensors of this outlet and all thresholds, such
as current, voltage, upper critical threshold, upper warning threshold, lower critical threshold, lower
warning threshold, and so on.
5. To make the Legrand PDU send SNMP notifications, select "System SNMP Notification Action" in the
Available Actions field.