Legrand PDU User Guide 373
config:#
sensor ocp <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the overcurrent protector that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the specified threshold for the
overcurrent protector sensor.
disable
Disables the specified threshold for the
overcurrent protector sensor.
A numeric
value
Sets a value for the specified threshold of the
overcurrent protector sensor and enables this
threshold at the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for the specified overcurrent protector
sensor. See
"To De-assert" and Deassertion Hysteresis
(on page 477).
<as_value> is a number in samples that is assigned to the assertion timeout for the specified overcurrent
protector sensor. See
"To Assert" and Assertion Timeout
(on page 475).
Commands for Environmental Sensors
A sensor threshold configuration command for environmental sensors begins with
sensor externalsensor
.
You can configure various environmental sensor threshold settings at a time by combining multiple
commands. See
Multi-Command Syntax
(on page 381).
Set the Upper Critical threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an environmental sensor: