Ju
ne
20
18
122 Legrand PDU User Guide
State
Description
below lower warning
Lower Critical threshold <= "R" < Lower
Warning threshold
above upper warning
Upper Warning threshold < "R" <= Upper
Critical threshold
above upper critical
Upper Critical threshold < "R"
alarmed
The state sensor enters the abnormal state.
unavailable
The communication with the managed
sensor is lost.
-- OR --
DPX2, DPX3 or DX sensor packages are
upgrading their sensor firmware.
Note that for a contact closure sensor, the normal state depends on the normal setting you have configured.
Refer to the Environmental Sensors and Actuators Guide (or Online Help) for detailed information, which is
available on Raritan's
Support page
(
Managed actuator states:
State
Description
on
The actuator is turned on.
off
The actuator is turned off.
unavailable
The communication with the managed
actuator is lost.
-- OR --
DX sensor packages are upgrading their
sensor firmware.
Unmanaged sensor/actuator states:
State
Description
unmanaged
Sensors or actuators are physically connected
to the Legrand PDU but not managed yet.
Note: Unmanaged sensors or actuators will disappear from the web interface after they are no longer
physically connected to the Legrand PDU. To manage a sensor/actuator, go to
Peripherals
Finding the Sensor's Serial Number
A DPX environmental sensor package includes a serial number tag on the sensor cable.