Ju
ne
20
18
Legrand PDU User Guide 201
Send Sensor Report
You may set the Legrand PDU so that it automatically reports the latest readings or states of one or multiple
sensors by sending a message or email or simply recording the report in a log. These sensors can be either
internal or environmental sensors listed below.
Inlet sensors, including RMS current, RMS voltage, active power, apparent power, power factor and
active energy.
Outlet state sensors, which are available on outlet-switching capable PDUs only.
Overcurrent protector sensors, including RMS current and tripping state.
Peripheral device sensors, which can be any Raritan environmental sensor packages connected to the
Legrand PDU, such as temperature or humidity sensors.
An example of this action is available in the section titled
Send Sensor Report Example
(on page 208).
Operation:
1. Choose Device Settings > Event Rules >
.
2. Select "Send sensor report" from the Action list.
3. In the Destination Actions section, select the method(s) to report sensor readings or states. The number
of available methods varies, depending on how many messaging actions have been created.
The messaging action types include:
Log event message
Syslog
message
Send
a. If no messaging actions are available, create them now. See
Available Actions
(on page 196).
b. To select any methods, select them one by one in the Available field.
To add all available methods, simply click Select All.
c. To delete any methods, click a method's
in the Selected field.
To remove all methods, simply click Deselect All.
4. In the Available Sensors field, select the desired target's sensor.
a. Click the first
to select a target component from the list.
b. Click the second
to select the specific sensor for the target from the list.
c. Click
to add the selected sensor to the Report Sensors list box.
For example, to monitor the current reading of the Inlet 1, select Inlet 1 from the left field, and then select
RMS Current from the right field.
5. To report additional sensors simultaneously, repeat the above step to add more sensors.