382 Legrand PDU User Guide
config:#
sensor ocp 2 current upperCritical disable upperWarning 15
Results:
The Upper Critical threshold of the 2nd overcurrent protector's RMS current is disabled.
The Upper Warning threshold of the 2nd overcurrent protector's RMS current is set to 15A and enabled
at the same time.
Example 3 - Combination of SSID and PSK Parameters
This multi-command syntax configures both SSID and PSK parameters simultaneously for the wireless
feature.
config:#
network wireless SSID myssid PSK encryp_key
Results:
The SSID value is set to myssid.
The PSK value is set to encryp_key.
Example 4 - Combination of Upper Critical, Upper Warning and Lower Warning Settings
The following multi-command syntax configures Upper Critical, Upper Warning and Lower Warning
thresholds for the outlet 5 RMS current simultaneously.
config:#
sensor outlet 5 current upperCritical disable upperWarning enable
lowerWarning 1.0
Results:
The Upper Critical threshold of outlet 5 RMS current is disabled.
The Upper Warning threshold of outlet 5 RMS current is enabled.
The Lower Warning threshold of outlet 5 RMS current is set to 1.0A and enabled at the same time.
Load Shedding Configuration Commands
This section applies to outlet-switching capable models only.
A load shedding configuration command begins with
loadshedding
.
Unlike other CLI configuration commands, the load shedding configuration command is performed in the
administrator mode
rather than the configuration mode. See
Different CLI Modes and Prompts
(on page
271).