Chapter 7: Using the Web Interface
229
Load Shedding Mode
When a UPS supplying power to PX3TS switches into battery backup operation,
it may be desirable to switch off non-critical outlets to conserve UPS battery
life. This feature is known as load shedding.
Outlets that are turned off when load shedding is activated are called
non-critical outlets. Outlets that are not affected by load shedding are called
critical outlets. By default, all outlets are critical. To set non-critical ones, see
Setting Non-Critical Outlets
(on page 227).
When load shedding is activated, the PX3TS turns off all non-critical outlets.
When load shedding is deactivated, the PX3TS turns back on all non-critical
outlets that were ON before entering the load shedding mode.
Exception: If you once manually perform switch-off operation on any
non-critical outlets during the load shedding mode, those outlets will NOT be
turned back on when exiting the load shedding mode.
Activation of load shedding can be accomplished using the web interface,
SNMP or CLI, or triggered by the contact closure sensors.
Tip: It is better to check non-critical outlets prior to manually entering the load
shedding mode. The non-critical information can be retrieved from the Outlets
page. See
Outlets
(on page 220) or
Available Data of the Outlets Overview
Page
(on page 224).
You must have the following two permissions to perform the load shedding
commands.
•
'Change Pdu, Inlet, Outlet & Overcurrent Protector Configuration'
•
'Switch Outlet' permission for all
non-critical
outlets
To enter the load shedding mode:
1.
On the Outlets page, click
> Activate Load Shedding.
Note: In case PX3TS prevents you from performing this command, check
your permissions, especially whether you have the Switch Outlet permission
for ALL non-critical outlets.
2.
Click Activate on the confirmation message.
In the load shedding mode:
▪
You CANNOT power on any "non-critical" outlets.
▪
The lock icon
appears for "non-critical" outlets that WILL be
automatically powered on when deactivating the load shedding mode.
▪
The off icon
appears for outlets, critical or non-critical, that
WILL NOT be automatically powered on when deactivating the load
shedding mode.
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......