Chapter 7: Using the Web Interface
433
▪
The active energy sensor is reset.
For example, when the Inlet I1's voltage exceeds the upper warning
threshold, the SNMP notifications are sent, and when the voltage drops
below the upper warning threshold, the SNMP notifications are sent again.
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want PX3TS to activate the load shedding function when a
contact closure sensor enters the alarmed state. This event rule requires
creating a new action before creating the rule.
Step 1: create a new action for activating the load shedding
1.
Choose Device Settings > Event Rules >
.
2.
In this illustration, assign the name "Activate Load Shedding" to the new
action.
3.
In the Action field, select "Change load shedding state."
4.
In the Operation field, select "Start load shedding."
5.
Click Create to finish the creation.
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......