Appendix A: Specifications
723
Relative humidity
10%-90% non-condensing
Operating altitude (above sea level)
0 feet (0 m) to 8500 feet (2591 m)
Compliance
UL 60950-1
Fuse types
Different models use different fuse types. You
must use the fuses listed below or equivalent
according to the rating of your models:
▪
16A models: Bussmann FWC-32A10F
(32A/600V)
Raritan part number: 557-90-0036-00
▪
24A or 32A models: Bussmann
FWP-50A14F (50A/660V)
Raritan part number: 557-90-0038-00
You can also find the appropriate fuse types
by checking the model names shown on the
Raritan-provided fuses accompanying your
PX3TS models.
Maximum Ambient Operating Temperature
The maximum ambient operating temperature (TMA) for PX3TS is 60 degrees
Celsius.
Serial RS-232 "RJ-45" Port Pinouts
RJ-45 Pin/signal definition
Pin No.
Signal
Direction
Description
1
RTS
Output
Request to send
2
DTR
Output
Data terminal ready
3
TxD
Output
Transmit data
4
GND
―
Signal ground
5
DCD
Input
Data
6
RxD
Input
Receive data (data in)
7
DSR
Input
Data set ready
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......