Appendix J: Additional PX3TS Information
841
In the threshold settings, the Deassertion Hysteresis field determines a new
level to trigger the "deassertion" action.
This function is similar to a thermostat, which instructs the air conditioner to
turn on the cooling system when the temperature exceeds a pre-determined
level. "Deassertion Hysteresis" instructs the PX3TS to de-assert the worse state
for a sensor only when that sensor's reading reaches the pre-determined
"deassertion" level.
For upper thresholds, this "deassertion" level is a decrease against each
threshold. For lower thresholds, this level is an increase to each threshold. The
absolute value of the decrease/increase is exactly the hysteresis value.
For example, if Deassertion Hysteresis = 2, then the deassertion level of each
threshold is either "+2" or "-2" as illustrated below.
Threshold value
Deassertion value
Upper Critical = 33
Deassertion level = 31
•
33 - 2 = 31
Upper Warning = 25
Deassertion level = 23
•
25 - 2 = 23
Lower Critical = 10
Deassertion level = 12
•
10 + 2 = 12
Lower Warning = 18
Deassertion level = 20
•
18 + 2 = 20
To use each threshold as the "deassertion" level instead of determining a new
level, set the Deassertion Hysteresis to 0 (zero).
Note: The difference between Upper Warning and Lower Warning must be at
least "two times" of the deassertion value.
How "Deassertion Hysteresis" is helpful:
If you have created an event rule that instructs the PX3TS to send notifications
for deassertion events, setting the "Deassertion Hysteresis" is helpful for
eliminating a number of notifications that you may receive in case a sensor's
readings fluctuate around a certain threshold.
Deassertion Hysteresis Example for Temperature Sensors
Summary of Contents for Raritan PX3TS
Page 4: ......
Page 6: ......
Page 20: ......
Page 80: ...Chapter 4 Connecting External Equipment Optional 60...
Page 109: ...Chapter 5 PDU Linking 89...
Page 117: ...Chapter 5 PDU Linking 97...
Page 441: ...Chapter 7 Using the Web Interface 421...
Page 464: ...Chapter 7 Using the Web Interface 444...
Page 465: ...Chapter 7 Using the Web Interface 445 Continued...
Page 746: ...Appendix A Specifications 726...
Page 823: ...Appendix I RADIUS Configuration Illustration 803 Note If your PX3TS uses PAP then select PAP...
Page 828: ...Appendix I RADIUS Configuration Illustration 808 14 The new attribute is added Click OK...
Page 829: ...Appendix I RADIUS Configuration Illustration 809 15 Click Next to continue...
Page 860: ...Appendix J Additional PX3TS Information 840...
Page 890: ...Appendix K Integration 870 3 Click OK...
Page 900: ......