Chapter 2: Rackmount, Inlet and Outlet Connections
12
3.
Secure with the provided end cap screws.
4.
On a 2U model, repeat the above steps to install another cable-support
bar.
5.
Fasten the rackmount brackets' ears to the rack using your own fasteners.
Inlet and Outlet Power Connections
The PX3TS connects to two different, but identically rated, branch circuits.
The PX3TS will operate when the branch circuit voltages are out of phase, but
works most reliably and fastest when in phase. The front panel Phase Sync
lamp lights if inlets are out of phase.