Bypass voltage lower limit setting
(Note: Inside the broken line is
the flashing part.)
Buzzer Settings (note: red dashed
box is the scintillation part
In the bypass voltage upper limit setting press “ON” or
in parallel ID setting press “OFF”, it goes to the bypass
lower limit setting. The bypass lower limit line flashes as
in above picture. (“-” for negative, positive does not have
any symbol.)
1. Use button “
” to set the different bypass voltage
lower limit. The bypass voltage lower limit range is
10%, 20%, 30%, 45%.
2. Press “ON” to exit the bypass voltage lower limit
setting and save the bypass voltage lower limit set-
ting value and goes to buzzer mute setting.
3. Press “OFF” to exit the bypass voltage lower limit
setting and goes to bypass upper limit setting.
In the bypass voltage low limit setting press “ON” or in
battery self-test setting press “OFF”, it goes to buzzer
setting. The scintillation of setting state shows as the
figure (Note: ON shows MUTE, OFF shows NO MUTE).
1. Press button “
” for Mute Cycle Settings, mute
choice has On and Off.
2. Press button “ON” exits mute setting and save
mute setting state and change to battery self-test
settings.
3. Press button “OFF” exits mute setting and change
to bypass voltage lower limit setting.
4.4.7 Bypass voltage lower limit setting
4.4.8 Buzzer Mute Setting