8.2
Messages
In this paragraph the messages that appear on the unit’s display are listed, also giving the most likely
cause that could have generated them.
If you are unable to solve the problem then please contact the Technical Service.
FIRST LINE OF THE MAIN FRAME
MESSAGE
MEANING
BUZZER OFF
The buzzer is turned off.
SERVICE MODE
UPS in the Service Mode. All settings via the display, maintenance functions
and updates are possible.
BATTERIES BEING CHARGED The UPS is charging the batteries. The load is not fed.
MAINTENANCE REQUIRED
Have specialized personnel carry out the routine check on the UPS.
CHECK THE BATTERIES
Have specialized personnel check battery status.
3V BATTERY FLAT
The control board’s 3V battery is
fl
at.
OUTPUT/PHASE OFF
Phase or output o
ff
Con
fi
guration achieved via the display or subsequent to
a UPS malfunction.
BACKUP IN STANDBY
UPS set as a backup and output o
ff
.
BYPASS INPUT KO
Bypass input KO; some problems have arisen on the Bypass line.
It is not possible to feed the loads directly o
ff
the mains.
UPS IN BYPASS
UPS in Bypass. The load is not protected by the UPS in this con
fi
guration.
FORCED BYPASS
The UPS has entered the forced Bypass mode via con
fi
guration on the display.
Load not protected by the UPS.
MANUAL BYPASS
The load is powered directly by the mains via a manual bypass.
In this con
fi
guration the load is not protected by the UPS.
UPS OFF-LINE
The load is powered directly by the bypass line. The load is protected because if there
is a power failure with the line it switches the load over to battery.
UPS ON BATTERY
UPS on battery. The cause for this con
fi
guration is a failure in the UPS feeding system
or a mains power failure.
BATTERY CALIBRATION
The UPS is calibrating the batteries by means of a command on the display.
BATTERY TEST
The UPS is testing the batteries to check their status and that they are working properly.
BATTERY EQUALIS.
The UPS is equalising the batteries.
BATTERY TEST.
The UPS is testing the batteries to check their status and verify they
are working properly.
REFERENCE MALFUNCTION
Synchronisation error between the commands.
AUTONOMY RESERVE!
Battery charge level is at minimum. The unit is about to shutdown.
BATTERIES KO
Batteries failed. Check their operation and replace them if necessary.
RUNAWAY BATTERIES
Battery voltage out of control.
Either the batteries or battery charger are/is malfunctioning.
HVBUS RUNAWAY FAILURE
A failure with the UPS has caused a voltage level on the High Voltage Bus
that is out of control.
OUT DC LEVEL FAILURE
A failure with the UPS has caused a DC voltage in output.
OVERHEATING
The temperature inside the UPS is out of the nominal range.
OVERLOAD
The total load is higher than the UPS’s nominal power. The UPS switches to Bypass
if there is voltage on the bypass line otherwise it shuts down.
Summary of Contents for Trimod 10 kVA
Page 1: ...Trimod Operating and Maintenance Manual Part LE05768AA 07 12 01 GF ...
Page 2: ... 2 EN ENGLISH 3 Trimod ...
Page 12: ...12 UPS Trimod 10 UPS Trimod 10 15 20 2 3 Models 2 Technological description ...
Page 13: ...Trimod Operating and Maintenance Manual 13 UPS Trimod 10 15 20 UPS Trimod 30 TT ...
Page 14: ...14 UPS Trimod 30 TM UPS Trimod 40 2 Technological description ...
Page 15: ...Trimod Operating and Maintenance Manual 15 UPS Trimod 60 ...
Page 16: ...16 2 Technological description UPS Trimod BATTERY UPS Trimod BATTERY 2 ...
Page 42: ...42 5 Installation UPS Trimod 30TM ...
Page 43: ...Trimod Operating and Maintenance Manual 43 UPS Trimod 30TT ...
Page 44: ...44 UPS Trimod 40 60 5 Installation ...
Page 46: ...46 5 Installation ...