28
6.2
Service Mode
This is the operating mode necessary to make the setup during the installation and to manage the software update of the
command board and power modules.
To access this mode, press the ENTER key with the the EPS off until the display shows the text "Service Mode...” At the end
of the start-up procedure, press the ENTER key to access the navigation menu.
It is possible to choose one of the following languages for the text displayed: Italian, English, German, French, Russian,
Spanish, Polish and Portuguese. Follow the path: UPS Setup
Operator Panel
Language and press the ENTER key
to confirm the choice.
Press the ON/OFF key to exit. Alternatively, the EPS turns off automatically after 20 minutes without receiving manual or
serial commands.
6.3
Main screen
The main screen is shown on the display during EPS operation.
Using the ARROW UP and ARROW DOWN keys it is possible to scroll through the different pages. Every page gives several
information about the status of the equipment.
The pictures of the different pages of the main screen are shown below:
MAIN PAGE
DATA DISPLAYED
1 input - output - battery
1st line: Operating status of the EPS. If the text alternates "TRIMOD
MCS” and “EPS in stand-by”, the output is disabled
2nd line: Input voltages
3rd line: Voltage set on output, active power absorbed by the load
and total percentage of the load applied.
4th line: Bar showing the battery residual capacity and the actual
operation time in case of a power failure.
2 input - percentage output - battery
1st line: Operating status of the EPS. If the text alternates
"TRIMOD MCS” and “EPS in stand-by”, the output is disabled
2nd line: Input voltages
3rd line: Percentage of the load on the output phases
4th line: Bar showing the battery residual capacity and the actual
operation time in case of a power failure.
3 bypass - output - battery
1st line: Operating status of the EPS. If the text alternates "TRIMOD
MCS” and “EPS in stand-by”, the output is disabled
2nd line: Bypass voltages
3rd line: Voltage set on output, active power absorbed by the load
and total percentage of the load applied.
4th line: Bar showing the battery residual capacity and the actual
operation time in case of a power failure.
4 bypass - percentage output - battery
1st line: Operating status of the EPS. If the text alternates "TRIMOD
MCS” and “EPS in stand-by”, the output is disabled
2nd line: Bypass voltages
3rd line: Percentage of the load on the output phases
4th line: Bar showing the battery residual capacity and the actual
operation time in case of a power failure.
6. Control panel
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...