34
Output
Voltage
This sets the output voltage value [V]
Frequency
Nominal
value (*)
This makes it possible to set the output frequency value
(50 Hz or 60 Hz) independently of the input frequency.
Auto
selection
If enabled, the EPS detects the frequency of the input
voltage and synchronises the output to the same value.
If disabled, the EPS uses the "Nominal Value” setting.
Inverter (*)
This sets the output configuration and the applied load:
- Single Phase: a unique single phase output
- Three Phases 120°: three phase output suitable for the supply of three
phase loads (e.g. a motor)
- Three Phases indep.: three single phase output lines that are independ-
ent of each other
Phases in startup (**)
L1 phase
This makes it possible to program the start-up status for
each output:
- Always ON: phase always on during start-up
- Always OFF: phase always off during start-up
- Last state: phase restored to the status prior to the
shutdown
L2 phase
L3 phase
(*) Available in the “Service Mode” only
(**) Available with the inverter set up as three independent phases only
WARNING
Only a skilled technician is authorized to modify the settings on the Output menu
Input
PLL enable
If enabled, the EPS synchronises the output pure sine with that of the
input.
If disabled, the output voltage is not synchronised with the input and it
is indicated with the status light (green) flashing.
PLL Range
This makes it possible to select the frequency range in which the EPS
synchronises the output voltage with the input:
- NORMAL: syncronization for frequency variations of ±2% of
the nominal value
- EXTENDED: syncronization for frequency variations of ±14% of the
nominal value
- CUSTOM: this can be set by the user (see the next menu item)
Custom PLL Range °
This makes it possible to set the customised frequency interval in which
the EPS synchronises the output voltage with the input.
The value can be selected from a minimum of 0.5 Hz to a maximum of
7.0 Hz with 0.1 Hz step
Input Dip Enable
This allows the input Dip function to be enabled/disabled
° Available with PLL range set in CUSTOMISED mode
INDICATION
The PLL function ensures that the output frequency is synchronised with that of the input, guaranteeing that passage
through zero (zero-crossing) occurs at the same moment. The input-output synchronisation is guaranteed even in case of
bypass intervention (e.g. because of overload).
INDICATION
By disabling the PLL function, the automatic bypass function is deactivated as well.
The equipment turns off in case of an extended overload.
WARNING
Only a skilled technician is authorized to modify the settings on the Input menu
6. Control panel
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...