Trimod MCS
U
ser manual
35
Bypass
Bypass enable
If enabled, the EPS manages the bypass intervention automatically.
If disabled, the EPS never switches to bypass mode so in the case of an
extended overload or in the case of failure and absence of redundancy,
it turns off.
Forced Mode
If enabled, the EPS activates the bypass permanently
DIP speed
It allows to vary the switching circuit sensitivity:
- SLOW: indicated for loads that are not sensitive to voltage fluctuations
and that cause current peaks
- STANDARD: normal mode
- FAST: for all loads that are highly sensitive to voltage fluctuations
Off-Line Mode
If enabled, the EPS operates in eco mode.
During the operation, the load is powered directly by the automatic
bypass circuit. If there is a power failure or the voltage input tolerance
is exceeded, the EPS activates the inverter thereby powering the load
through the batteries.
Startup on Bypass
If enabled, on mains start-up the initial powering of the load occurs via
bypass.
If disabled, the inrush current is managed by the inverter as in a battery
start-up.
WARNING
Only a skilled technician is authorized to modify the settings on the Bypass menu
Batteries
Threshold Values
Reserve Time
This sets the start time of the battery autono-
my warning [min]
MaxTime on Battery
This sets the maximum operating time in
battery mode. Once this time has elapsed,
the EPS turns off. Set at OFF to disable the
function
Charger
Standby Charge
If enabled, it activates the battery charge
with the EPS off
Auto Restart
Restart Enable
This enables or disables the restart of the
EPS when the mains returns after the total
discharge of the batteries
Min. Autonomy
This sets the percentage charge value
of the batteries to be reached with the
standby charge function in order to restart
automatically the EPS after a total battery
discharge.
Total KB
This sets the total number of KB installed. The parameter is necessary
for the EPS to provide correct values for the autonomy based on the
load applied and for a correct battery charge.
Capacity (*)
This sets the capacity value of the batteries in the EPS [Ah].
(*) Available in the “Service Mode” only
WARNING
Only a skilled technician is authorized to modify the settings on the Batteries menu
Summary of Contents for Trimod MCS 10
Page 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Page 2: ...2 UK ENGLISH 3 Trimod MCS ...
Page 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Page 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Page 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Page 58: ...58 ...
Page 59: ...Trimod MCS User manual 59 ...