Over Current Protection: 

The BZ-150 contains built-in short circuit and thermal protection circuitry that 
shuts down the +24VDC output (low voltage red wire) to prevent permanent 
damage to the power pack. Removing the excess load from the output restores 
the BZ-150 to proper operation. Connect the excess load to another power pack.

LED Indicator 

The LED on the reverse side of the BZ-150 indicates the following conditions:

• 

LED OFF:

  no power to the BZ-150, or the +24VDC output is shorted.

• 

LED blinking continuously:

 current output limit is exceeded (too many 

sensors are connected to the power pack); +24VDC output shut down.

• 

LED ON, blinks once every 4 or 5 seconds:

  the relay is closed (load ON).

• 

LED ON continuously:

 the relay is open (load OFF).

TROUBLESHOOTING

The lights came ON automatically after I deliberately turned them 
OFF for a presentation.

•  The BZ-150 is set for the Auto ON Mode and the occupancy sensor time delay 

expired. The BZ-150 reverted to Auto ON and then motion was detected. 

 

-- Consider increasing occupancy sensor sensitivity and/or time delay.
-- Generate more motion during presentations.

The load does not turn ON with occupancy detection.

•  Mode Switch is set to Manual ON.

•  Hold OFF input is active.

The load does not turn OFF after sensor time delay expires.

•  Hold ON input is active.

The load does not respond when I press the momentary switch.

• Check 

wiring.

The load does not come on automatically although the Mode Switch is 
set to Auto ON.

•  Cycle power to the unit to reset operating mode to Auto ON. Mode Switch 

location was changed while the power pack was was powered (line voltage).

The load comes on automatically with occupancy although the Mode 
Switch is set to Manual ON.

•  Cycle power to the unit to reset operating mode to Manual ON. Mode Switch 

location was changed while the power pack was was powered (line voltage).

Summary of Contents for WattStopper BZ-150

Page 1: ...quirements Ballast 20amp 120 277VAC Incandescent 20amp 120VAC Motor 1HP 120 240VAC Output 225mA 24VDC with relay connected Low Voltage Input Control ON 12 24VDC Hold ON 12 24VDC Hold OFF 12 24VDC Manual ON momentary switch required 12 24VDC Operating Temperature 32 104 F 0 40 C Santa Clara CA 95050 ...

Page 2: ... After initial wiring is complete check wiring diagrams to verify the power pack is wired correctly Improper wiring can cause damage to the power pack lighting system occupancy sensor and other control devices INSTALLATION WARNING TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS WIRING Low Voltage High Voltage 24VDC Common Red White Neut Power Pack Blue Black Red Dry Contact Lightin...

Page 3: ...xpires e g as might be required for a presentation Pressing the momentary switch before the sensor time delay expires turns ON the load When the occupancy sensor s time delay expires the BZ 150 reverts to Auto ON mode and it turns ON the load with the next input from the occupancy sensor Manual ON Mode Switch RIGHT Occupants must press the low voltage momentary switch to turn ON the load When the ...

Page 4: ... inputs Momentary Input Manual ON OFF Grey This input is for a low voltage momentary switch Applying 12 24VDC momentary input changes the relay to the opposite state It overrides Control ON Hold ON and Hold OFF inputs BI LEVEL CONTROL WITH MANUAL ON The diagram to the right shows how to configure BZ 150s to provide bi level lighting control with both Automatic ON and Manual ON features As shown upo...

Page 5: ...them OFF for a presentation The BZ 150 is set for the Auto ON Mode and the occupancy sensor time delay expired The BZ 150 reverted to Auto ON and then motion was detected Consider increasing occupancy sensor sensitivity and or time delay Generate more motion during presentations The load does not turn ON with occupancy detection Mode Switch is set to Manual ON Hold OFF input is active The load doe...

Page 6: ...her indirect damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 2800 De La Cruz Boulevard Santa Clara CA 95050 Technical Support 800 879 8585 www wattstopper com 08616r3 6 2009 ORDERING INFORMATION Load Range Catalog No Description Input Voltage Ballast A Incan A Motor hp Output BZ 50 Power Pack 120 230 277VAC 50 60Hz 20 20 1 24VDC 225mA w r...

Reviews: