2
WIRING
The ground terminal must be connected to ground for the AS-100 to function. Never connect the AS-100 to a power pack; always
connect the AS-100 to a lighting control panel.
Hot
Neutral
Load
Lighting
Control
Panel
Line
Ground
No connection for
this application. *
Line
Ground
Load
3-
Wa
y
Signal Wire**
Wiring a single switch to
a lighting control panel
Line
Ground
Ground
Do not connect
to line voltage*
Line
Ground
Load
3-
Wa
y
Line
Ground
Load
3-
Wa
y
Hot
Lighting
Control
Panel
Line
Remote Switch
Master Switch
No Load
Connection
Load
Neutral
Do not connect
to line voltage*
Signal
Wire**
Signal Wire**
Neutral
Wiring for 3-way operation with a lighting control panel
SETUP
The AS-100 Automatic Control Switch comes factory preset and ready to install in conjunction with a lighting control panel. The default
operation is manual-ON/OFF along with automatic-OFF when signaled by the lighting control panel.
NOTE:
Setup options apply to Master Switch only under 3-way operation.
If an audible beep warning or automatic-ON features are desired, use the following procedure:
• Setup for the switch options is accomplished with the ON/OFF button and LED display. There is no need to remove the cover plate.
1. To enter Setup Mode: Press and hold down the ON/OFF button until the LEDs flash every second from left to right (approximately
7 seconds).
2. When in Setup Mode, the configuration LEDs flash to indicate the current configuration settings. Press the ON/OFF button to
sequence through the option selections until the desired options are displayed.
3. To exit Setup Mode and save the selected options: Press and hold the ON/OFF button until the LEDs flash every second from
right to left (approximately 3 seconds). If the lights controlled by this switch are ON, the lighting fixtures will turn OFF. Setup is now
complete and the option selections are saved.
If the ON/OFF button is not pressed to exit Setup Mode, the AS-100 will time out of Setup Mode after approximately 30 seconds,
and new option selections will not be saved.
Factory Settings:
• Lighting control panel automatic-
OFF capable.
• No Setup Mode options are
selected.
• See Operation (next page) for
other available functions.
$XWRPDWLF21
$XGLEOHEHHS
GXULQJ$XWRPDWLF'HOD\HGRII
6HWXS0RGH2SWLRQV
/('GLVSOD\
2SWLRQLVRQZKHQ/('IODVKHVLQGLVSOD\
6HWXS0RGHRSWLRQVRIIIDFWRU\VHWWLQJ
$XGLEOHEHHSRSWLRQRQ
$XWRPDWLF21RSWLRQRQ
$XWRPDWLF21 $XGLEOHEHHSRSWLRQVRQ
8QXVHG
* Never connect line voltage to the 3-Way terminal. Doing so will damage the AS-100 and void the warranty.
**Signal Wire (Blue with White Stripe) connects to Neutral. For a replacement or retrofit application , it can connect to Ground.