background image

2

WIRING

The ground terminal must be connected to ground for the AS-100 to function. Never connect the AS-100 to a power pack; always 

connect the AS-100 to a lighting control panel.

Hot

Neutral

Load

Lighting

Control

Panel

Line

Ground

No connection for

this application. * 

Line

Ground

Load

3-

Wa

y

Signal Wire**

Wiring a single switch to  

a lighting control panel

Line

Ground

Ground

Do not connect

to line voltage* 

Line

Ground

Load

3-

Wa

y

Line

Ground

Load

3-

Wa

y

Hot

Lighting

Control

Panel

Line

Remote Switch

Master Switch

No Load

Connection

Load

Neutral

Do not connect

to line voltage* 

Signal

Wire**

Signal Wire**

Neutral

Wiring for 3-way operation with a lighting control panel

SETUP

The AS-100 Automatic Control Switch comes factory preset and ready to install in conjunction with a lighting control panel. The default 

operation is manual-ON/OFF along with automatic-OFF when signaled by the lighting control panel.

NOTE: 

Setup options apply to Master Switch only under 3-way operation.

If an audible beep warning or automatic-ON features are desired, use the following procedure:

•  Setup for the switch options is accomplished with the ON/OFF button and LED display. There is no need to remove the cover plate.
1.  To enter Setup Mode: Press and hold down the ON/OFF button until the LEDs flash every second from left to right (approximately 

7 seconds).

2.  When in Setup Mode, the configuration LEDs flash to indicate the current configuration settings. Press the ON/OFF button to 

sequence through the option selections until the desired options are displayed.

3.  To exit Setup Mode and save the selected options: Press and hold the ON/OFF button until the LEDs flash every second from 

right to left (approximately 3 seconds). If the lights controlled by this switch are ON, the lighting fixtures will turn OFF. Setup is now 

complete and the option selections are saved.
If the ON/OFF button is not pressed to exit Setup Mode, the AS-100 will time out of Setup Mode after approximately 30 seconds, 

and new option selections will not be saved.

Factory Settings:

•  Lighting control panel automatic-

OFF capable.

•  No Setup Mode options are 

selected.

•  See Operation (next page) for 

other available functions.

$XWRPDWLF21

$XGLEOHEHHS

GXULQJ$XWRPDWLF'HOD\HGRII

6HWXS0RGH2SWLRQV

/('GLVSOD\

2SWLRQLVRQZKHQ/('IODVKHVLQGLVSOD\

 6HWXS0RGHRSWLRQVRIIIDFWRU\VHWWLQJ

 $XGLEOHEHHSRSWLRQRQ

 $XWRPDWLF21RSWLRQRQ

 $XWRPDWLF21 $XGLEOHEHHSRSWLRQVRQ

 8QXVHG

* Never connect line voltage to the 3-Way terminal. Doing so will damage the AS-100 and void the warranty.
**Signal Wire (Blue with White Stripe) connects to Neutral. For a replacement or retrofit application , it can connect to Ground.

Reviews: