background image

         WWW.LEGRAND.US/WATTSTOPPER - IS-00709-D  Commercial Enclosure Solutions — MODEL: LCAP44/A & LCAP44/A + Main Lug 

page 1 of 8 

Commercial Power Enclosure Solutions and Main Lug Options — LCAP MODEL: LCAP44A 

LCAP WITH MAIN LUG MODELS: LCAP44ALO/MLO/MCB

The VA-RUU-1 switch comes pre-installed in KIT. 

The VA-EPC-DFS-1 switch is installed on site. 

NOTE: Please see install sheets for emergency 
 switch 

applications. 

EMR. SWITCH 

VA-EPC-DFS-12OV(277V) 

Order  Separate 

EMR. SWITCH 

VA-RRU-1-12OV (277V)

LCAP-OPT-SWITCH 

8-Port (4 standard and 4 POE)

Overview 

The 

Wattstopper

®

 LCAP Series Commercial Enclosures

 ship with pre-configured 

modular solutions. Load dimming and switching use the InFusion™ controllers 
and switching products. The pre-configured designs save time in the 

Design 

Center

™ software and during the installation process.  

 
The UL listed LCAP44A panels are adaptable to spaces that have mixed 0-10V, 
and PWM loads and HV relay loads via the LVOS-0-10-PWM station. LCAP44A 
connects to any controller over the local network for easy connection and 
scalability. 
 

Solution 1 – Parent-level Enclosure Models 

Main Enclosure 

Description 

LCAP44 

44” Architectural Enclosure with hinged cover door 

LCAP44A Panel 

Configurations 

 

(see KIT panel 

part numbers 

ordering key 

last page) 

Panel 

Upper

 Section: 

 

1 to 2 LVOS-0-10-PWM stations 

Panel 

Middle

 Section: 

 

1 to 2 LVOS-0-10-PWM stations 

Panel 

Lower

 Section: 

 

1 to 2 LVOS-0-10-PWM stations 

Panel 

Low-Voltage

 Section

 

Optional Parts 

Description 

LCAP-OPT-SWITCH  8-Port (4 standard and 4 POE) Ethernet switch/power supply 

VA-RRU-1-120V 

Emergency Shunt Relay - 120V 

VA-RRU-1-277V 

Emergency Shunt Relay - 277V 

Additional  Parts Ordered Separately 

Description 

VA-EPC-DFS-120V 

Emergency lighting surface mount switch 120V 

VA-EPC-DFS-277V 

Emergency lighting surface mount switch 277V 

 
Specifications 

LCAP44A 

Specifications 

Cabinet Dimensions HWD 

44.5” x 24” x 4.575” / 113cm x 61cm x 11.6cm 

Door Dimensions HWD 

44.5” x 24” x 0.75” / 113cm x 61cm x 2cm 

Panel Insert HWD 

42” x 21” x 4.175” / 106.7cm x 53.3cm x 10.6cm 

Weight Enclosure 

41 lbs / 18.6 kg 

Weight Door 

20.7 lbs / 9.39 kg 

Weight Panel Insert 

23 lbs / 10.43 kg 

Number of LVOS-0-10-PWM* stations 

Up to 6 

Analog, 0-10DC/LV — Max. Outputs 

Up to 24 

PWM, LV — Max. Outputs 

Up to 24 

HV Relay 120-277 VAC — Max. Outputs 

Up to 24 

Line Feeds (breakers) required 

1 and Up 

Enclosure Finish 

Galvanized Steel 

Door Finish 

Black - Powder Coated 

Cover 

vented, hinged 

HV Wire 

copper wire, min of 80°C/176°F insulation 

Ventilation 

maintained 36” front clearance 

Ambient Operating Temp. 

0-40°C / 32-104°F 

Ambient Operating Humidity 

5-95% non-condensing 

UL, CUL, and CE listed 

yes 

 
*

 See these install sheets for important information: 

 

Low Voltage Output Station Lighting_LVOS-0-10-PWM-1 

 

LCAP Enclosure Designs

 

LCAP Series Enclosure Facts. 

 

Enclosures must be populated from 

left to right

 and 

top down

.  

o

  Blank positions cannot be left between lighting modules in Design 

Center setup.  

  Enclosures are pre-configured and wired (to the extent possible) using 

specific combinations of the following components. Installed components are 
dependent on the enclosure design.  

o

  Components using high voltage wiring.  

  Mixed high voltage wiring. 

o

  Components using low voltage control signal wiring. 

o

  Components using low voltage communication wiring. 

o

  Components using high voltage and low voltage connections made 

inside the enclosure. 

 

The enclosure uses built-in barriers to separate high and low voltage wiring. 

o

 Some designs include the barrier while other designs require the 

barrier be added by the designer. 

o

  High voltage barriers may be installed between 120V/240V/277V load 

modules. 

 

LCAP44A Enclosures only contain LVOS-0-10-PWM stations.

  

 

Enclosure Features / Parts 

 

1.  Enclosure can (includes door), order 

LCAP44

 for can only. 

2. Panel 

Insert 

(upper section)

a. Ground terminals, 

(notice terminals for all sections)

b. Wiring terminal blocks for upper section LVOS stations, 

(notice wiring 

blocks for all sections if populated with LVOS stations)

i. Internal 

side 

pre-wired 

(see Wiring Block pg. 2)

ii. 

External side wired in field 

(see Wiring Block pg. 2)

c.  Up to 2 LVOS-0-10-PWM stations (upper section) 

3. Panel 

Insert 

(middle section)

a.  Up to two 

additional

 LVOS-O-10-PWM stations. 

4. Panel 

Insert 

(lower section)

a.  Up to two 

additional

 LVOS-O-10-PWM stations. 

5. Panel 

Insert 

(low-voltage section)

6.  Enclosure cover with hinged/vented door allowing easy access when 

servicing and proper ventilation for convection cooling process. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

LCAP44A Panel Optional  
Construction Parts See  
Ordering Key,  
last page. 

 
 
 
 

Installation / Enclosure Mounting Instructions

 

Installation of LCAP products should be performed or supervised by a 
Wattstopper factory representative

Installation and maintenance of high voltage 

devices should only be performed by 

qualified

 and 

licensed p

ersonnel having 

appropriate training and experience. 

 
General Wiring 
Drill proper size holes in can for running wires in and out of 
the enclosure. Separate high and low voltage wire run 
channels.

 All wire runs in and out of the enclosure should be 

secured

 using 

2-screw connectors

 or equivalent as shown at 

the right 

Proper conduit or equivalent wire channels 

should be used according to local codes and regulations. 
 

IMPORTANT SAFEGUARDS 
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 
 
CAUTION: 

Turn Breakers 

OFF

 and check that no power is on at the AC 

Terminal Boards when working in the enclosure or working on 
lighting fixtures connected to the module’s loads, etc. Do not 
allow trimmed wire cuttings to fall into enclosure components as 
they may cause damage when power is restored. Damage from 
this type of short will 

void

 the warranty. 

 

Do not use outdoors. 

 

Do not mount near gas or electric heaters. 

Wattstopper

®

Summary of Contents for Wattstopper LCAP Series

Page 1: ...ries Enclosure Facts Enclosures must be populated from left to right and top down o Blank positions cannot be left between lighting modules in Design Center setup Enclosures are pre configured and wir...

Page 2: ...M P 1 with 5 pre wired blocks optional 1 COM POE SWITCH Ethernet sw 1 to 5 VA RRU 1 120V or VA RRU 1 277V LCAP44A 6 KIT included 1 LCAP44A panel 6 LVOS 0 10 PWM P 1 with 6 pre wired blocks optional 1...

Page 3: ...ug Panel options range from 18 to 36 circuits 208 480V and 10kAIC to 65kAIC and may be configured with a main breaker option Setup In Design Center Understanding LCAP and Main Lug panels LCAP panels w...

Page 4: ...44ALO Panel 2 Enclosure lower section for up to 18 breakers Select the Main Lug option MLO option for up to 18 20A breakers 3 Breaker section may be configured for 4 wire or 3 wire power configuration...

Page 5: ...ain Lug option MLO option for up to 36 20A breakers 3 Breaker section may be configured for 4 wire or 3 wire power configurations See last page for breaker order options LCAP44 1 8 PANEL SURFACE MOUNT...

Page 6: ...umber Ordering Key Design Center will generate LCAP44ALO MLO MCB part numbers automatically as the enclosures are built This key is for help in understanding and creating orders in the LCAP Quote Tool...

Page 7: ...WWW LEGRAND US WATTSTOPPER IS 00709 F Commercial Enclosure Solutions MODEL LCAP44A LCAP44ALO Main Lug page 7 of 8...

Page 8: ...WWW LEGRAND US WATTSTOPPER IS 00709 F Commercial Enclosure Solutions MODEL LCAP44A LCAP44ALO Main Lug page 8 of 8...

Reviews: