WWW.LEGRAND.US/WATTSTOPPER - IS-00709-D Commercial Enclosure Solutions — MODEL: LCAP44/A & LCAP44/A + Main Lug
page 2 of 8
PANEL
BACK VIEW
MULTI-VIEW
LCAP44A–
LCAP44A - Architectural Panel -
Auxiliary
*
LVOS-0-10-PWM - select quantity: select -
(Leave blank for
0
) 1, 2, 3, 4, 5, or 6
KIT PART NUMBERS:
LCAP44A-KIT
included 1
LCAP44A
panel
optional 1 COM-POE-SWITCH Ethernet sw
LCAP44A-1-KIT
included 1
LCAP44A
panel,
&
1
LVOS-0-10-PWM-P-1
with 1 pre-wired block
optional 1 COM-POE-SWITCH Ethernet sw, 1 VA-RRU-1-120V or VA-RRU-1-277V
LCAP44A-2-KIT
included 1
LCAP44A
panel,
&
2
LVOS-0-10-PWM-P-1
with 2 pre-wired blocks
optional 1 COM-POE-SWITCH Ethernet sw, 1 or 2 VA-RRU-1-120V or VA-RRU-1-277V
LCAP44A-3-KIT
included 1
LCAP44A
panel,
&
3
LVOS-0-10-PWM-P-1
with 3 pre-wired blocks
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 3 VA-RRU-1-120V or VA-RRU-1-277V
LCAP44A-4-KIT
included 1
LCAP44A
panel,
&
4
LVOS-0-10-PWM-P-1
with 4 pre-wired blocks
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 4 VA-RRU-1-120V or VA-RRU-1-277V
LCAP44A-5-KIT
included 1
LCAP44A
panel,
&
5
LVOS-0-10-PWM-P-1
with 5 pre-wired blocks
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 5 VA-RRU-1-120V or VA-RRU-1-277V
LCAP44A-6-KIT
included 1
LCAP44A
panel,
&
6
LVOS-0-10-PWM-P-1
with 6 pre-wired blocks
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 6 VA-RRU-1-120V or VA-RRU-1-277V
Do not mount enclosures in attics, garages, or crawlspaces, unless room is
properly conditioned to conform to ambient room temperature and humidity
requirements.
Mount enclosure a minimum of 18” from ceiling or floor.
National Electrical Code requires a minimum frontal clearance of 36” for the
enclosure.
Use screws provided for mounting.
If any emergency circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed
source of power during emergency and power outage situations.
LISTED AS EMERGENCY LIGHTING EQUIPMENT – using an appropriate
label.
CAUTION: To avoid electrical
overload, total external connected
load should not exceed output rating.
SAVE THESE INSTRUCTIONS
Wire Block Terminal Close Up
Part Number Ordering Key
Design Center will generate part numbers automatically as the enclosures are
built. This key is for help creating manual orders if needed
LCAP44A Enclosure Multi-View
EMERGENCY CIRCUITS