         WWW.LEGRAND.US/WATTSTOPPER - IS-00709-F  Commercial Enclosure Solutions — MODEL: LCAP44A & LCA Main Lug 

page 3 of 8 

LCAP Panels with Main Lug Panel OPTION 

 

LCAP44/A/LO/CB Panels with Main Lug Panel OPTION 
Main Lug Circuit Breaker Option 

The LCAPA and LCAPM series enclosures can be configured as a 

load

 feed 

through panel (LCAP PANEL only) or as main lug panels with the addition of load 
circuit breakers below the load control feed through compartment. Main lug 
options can also contain a main breaker. The Main Lug option is available for the 
LCAP

ALO

 and LCAP

MLO/SLO

 series panels – see the 

LCAP32/44/M/S

 install 

sheet. The circuit breaker options are based on the panel configuration, number 
and type of loads,

 

and circuit breaker rating requirements. Once the main lug 

panel and circuit breaker options are selected the panel is built and prewired

*

 in 

the factory and delivered to the project ready to be installed.

 

 
*NOTE:

 

Panels with GFI breakers

: GFI breakers are not installed or 

pre-wired and are shipped separately. 
 

Applications 

The LCAP44A is designed for medium to large spaces requiring control of up to 
24 low voltage PWM lighting circuits, 24 low voltage 010V DC lighting circuits, 
and 24 120-277VAC relay lighting circuits. The built-in integration and networking 
capabilities of the LCAP44A easily meet requirements in spaces needing multiple 
types of lighting, and other automation integration systems using this panel. 
Adding an Equinox 41 or 73 touchscreen to the project allows the facility 
manager or end user to create, change, and manage scenes, schedules, and 
user profiles. 

 
Features

 

 

Modular LCAP load section; pre-configured solution from the factory. Just 
connect line voltage and load wires. 

 

Pre-configured Main Lug Panel solution options. 

 

System is expandable using other LCAP series primary or secondary panels 
and LCAP Main Lug / Circuit Breaker options. 

 

Can be configured with emergency circuits for emergency lighting. 

 

Connects to InFusion Controller system via Ethernet or Station Bus. 

 

Up to 24 dry contact inputs; 12 of the contacts may be used for, system 
powered, light sensors or occupancy sensors. 

  Dimmers have programmable start/stop and dimming curve adjustment 

features to customize dimming linearity. 

 

Simple programming from a single software solution - Design Center. 

 

Adding one BACnet enabled controller to a system allows the entire system 
to be controlled through BACnet. 

 

Main Lug Panel options range from 18 to 36 circuits, 208-480V, and 10kAIC 
to 65kAIC and may be configured with a main breaker option. 

 

Setup In Design Center

 

Understanding LCAP and Main Lug panels

 

LCAP panels with the Main Lug option is a larger enclosure that holds the 
traditional LCAP components in the upper section of the enclosure and 
includes a breaker section in the lower section of the enclosure. 

 

LCAP panels with the Main Lug option are built in Design Center the same 
way as standard LCAP panels. The only difference is the Main Lug option 
has been selected. Follow the steps below to create an LCAP panel with the 
Main Lug option selected. 

 
1. In 

Design Center | Object Explorer

 select 

 

Vantage Objects,

 

 

Enclosures, Commercial,

 

 

LCAP model,

 

o

  LCAP44A-KIT (Main Lug),  

2. 

Right click in the enclosure and select 

Populate

 to automatically add LVOS-PWM 

stations

 

in the enclosure or select LVOS-

PWM stations

 

and drag into the enclosure 

as wanted. (It is not possible to drag an 
LVOS-PWM station below a blank station 
position in an LCAP enclosure – fill 
enclosure from left to right / top to bottom. 
Notice that breakers are automatically 
added to the 

Main Lug

 section of the 

enclosure as LVOS-PWM stations are 
added. 

3. 

It is possible to add additional breakers in 
the Main Lug section by right clicking 
below existing breakers and selecting Add 
Breaker until the maximum number of 
breakers allowed is reached. 

4. 

Select the Main Lug section of the 
enclosure and change the type to 

MCB

 to 

add a Main Breaker option or leave as 

MLO

 for standard load breakers only. 

 

 
LCAP44ALO/MLO/MCB Series Specifications 

Specifications 

LCAP44ALO/MLO 

LCAP44ALO/MCB 

Cabinet / Panel Cover Dimensions HWD 

68.0” x 24.0” x 4.75” 

172.72cm x 60.96cm x 12.06cm 

77.0” x 24.0” x 4.75” 

195.58cm x 60.96cm x 12.06cm 

Breakers 

Up to 18 

Up to 36 

Main Lug Panel Door Dimensions HWD 

16” x 12.5” x 0.75” 

40.64cm x 31.75cm x 1.9cm 

23” x 19” x 0.75” 

58.42cm x 48.26cm x 1.9cm 

Weight Enclosure with Cover 

165 - 175 lbs / 74.84 – 79.38 kg 

170 - 180 lbs / 77.11 – 81.65 kg 

LCAP Panel Door Dimensions HWD 

40.5” x 16.0” x 0.75”  /  102.87cm x 40.64cm x 1.9cm 

Panel Insert HWD 

42” x 21” x 4.175”  /  106.7cm x 53.3cm x 10.6cm 

Weight Panel Insert 

M-23 lbs. 10.43 kg 

Number of LVOS-0-10-PWM

*

 stations 

Up to 6 

Analog, 0-10DC/LV — Max. Outputs 

Up to 24 

PWM, LV — Max. Outputs 

Up to 24 

HV Relay 120-277 VAC — Max. Outputs 

Up to 24 

Enclosure Finish 

Galvanized Steel 

Door Finish 

Black - Powder Coated 

Cover 

vented, hinged 

Wire 

copper wire, MIN. of 80°C / 176°F insulation 

Ventilation 

maintained 36” front clearance 

Ambient Operating Temp. 

0-40°C / 32-104°F 

Ambient Oper. Humidity 

5-95% non-condensing 

UL, CUL, and CE listed 

yes 

 

Summary of Contents for Wattstopper LCAP Series

Page 1: ...ries Enclosure Facts Enclosures must be populated from left to right and top down o Blank positions cannot be left between lighting modules in Design Center setup Enclosures are pre configured and wir...

Page 2: ...M P 1 with 5 pre wired blocks optional 1 COM POE SWITCH Ethernet sw 1 to 5 VA RRU 1 120V or VA RRU 1 277V LCAP44A 6 KIT included 1 LCAP44A panel 6 LVOS 0 10 PWM P 1 with 6 pre wired blocks optional 1...

Page 3: ...ug Panel options range from 18 to 36 circuits 208 480V and 10kAIC to 65kAIC and may be configured with a main breaker option Setup In Design Center Understanding LCAP and Main Lug panels LCAP panels w...

Page 4: ...44ALO Panel 2 Enclosure lower section for up to 18 breakers Select the Main Lug option MLO option for up to 18 20A breakers 3 Breaker section may be configured for 4 wire or 3 wire power configuration...

Page 5: ...ain Lug option MLO option for up to 36 20A breakers 3 Breaker section may be configured for 4 wire or 3 wire power configurations See last page for breaker order options LCAP44 1 8 PANEL SURFACE MOUNT...

Page 6: ...umber Ordering Key Design Center will generate LCAP44ALO MLO MCB part numbers automatically as the enclosures are built This key is for help in understanding and creating orders in the LCAP Quote Tool...

Page 7: ...WWW LEGRAND US WATTSTOPPER IS 00709 F Commercial Enclosure Solutions MODEL LCAP44A LCAP44ALO Main Lug page 7 of 8...

Page 8: ...WWW LEGRAND US WATTSTOPPER IS 00709 F Commercial Enclosure Solutions MODEL LCAP44A LCAP44ALO Main Lug page 8 of 8...

Reviews: