Wattstopper
®
DLM - DLM GE SWS or TLC Relay to LMCP Retrofit Kits
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24813 – 11/16 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: LMCP-GE24/LMCP-GE48
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
LMCP-GE24 RETROFIT KIT INSTALLATION
Step 1:
Remove all interior components
leaving relays and power supply only.
Fig. 1: Example GE24
panel assembly
Fig. 2: After removing
interior items
Step 3:
Install LMRD adapter plate.
Fig. 4: Install LMRD adapter plate
Step 4:
Install LMRD and LMPI cards.
CAUTION:
Do not overtighten screws.
Fig. 5: LMRD and LMPI mounting details
Step 5:
• Connect LMRD card to LMPI.
• Connect relays to LMRD card.
• Connect power to LMPI.
(See
Relay Connection Details
for DIP Switch settings.)
Fig. 6: Connection details
Step 6:
Apply upgrade label.
Fig. 7: Label location suggestion
Step 2:
Remove LMRD cards
from adapter plate.
Fig. 3: Remove LMRD
Mounting plate
screw locations
(Total 4 #6-32
screws for
mounting plate)
LMRD-12-MP
P/N # 841436
LMRD-12
P/N # 16694
Mounting plate screw locations
(Total 12 #4-40 screws for
mounting plate)
Mounting plate screw locations
(Total 4 #6-32 screws for
mounting plate)
LMPI-ASSY
P/N # 770431
Power supply connection detail