background image

Wattstopper

 

®

Digital Lighting Management Low Voltage Dimming Wall Switch (v3)

Gestion numérique de l’éclairage Interrupteur mural basse tension à gradation (v3)

Regulador de pared de bajo voltaje DLM (v3)

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 23493 – 10/18  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMDM-101

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltage ................................................................................... 24VDC

Current Consumption ..................................................................5mA

Power Supply ...................................... Wattstopper Room Controller

Connection to the DLM Local Network ......................... 2 RJ-45 ports

DLM Local Network characteristics when using LMRC-11x/2xx room 
controllers:

 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ...................................................... For Indoor Use Only

 

Operating Temperature ......................32° to 131°F (0° to 55°C)

 

Storage Temperature ........................23° to 176°F (-5° to 80°C)

 

Relative Humidity ............................5 to 95% (non condensing)

Patent Pending

MOUNTING THE SWITCH

WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits.

This unit is pre-set for Plug n’ Go™ operation, 
adjustment is optional.

For full operational details, adjustment and more 
features of the product, see the DLM System Installation 
Guide provided with Wattstopper room controllers, and 
also available at www.legrand.us/wattstopper. 

Installation shall be in accordance with all applicable 
regulations, local and NEC codes. 

Wire connections 

shall be rated suitable for the wire size (lead and building 
wiring) employed. 
For Class 2 DLM devices and device wiring: To be 
connected to a Class 2 power source only. Do not 
reclassify and install as Class 1, or Power and Lighting 
Wiring.
Do not apply cleaning solvent directly onto unit. Apply 
cleaning solvent onto a cloth, then wipe the unit to clean it..

BUTTONS AND INDICATORS

Red LED

Blue load 
status LED

Tap when load OFF: Turn ON to last level
Tap when load ON: Go to full bright
Press & Hold: Ramp Up

Configuration Button 
(behind switch plate)

Tap: Fade to OFF
Press & Hold: Ramp Down

LEDs
show
light
level
setting

Rocker Panel

When all loads bound to the dimmer are OFF, the Blue load 
status LED is dim. A single light level LED is lit to show the last 
light level.

When any load bound to the dimmer is ON the load status 
LED is bright. The number of illuminated light level LEDs 
indicates the highest light level on any of those loads.

CONNECTIVITY

The illustrations here show examples of free-topology wiring. The LMDM communicate to all other Digital Lighting Management devices 
connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network. 

Line Voltage

Line Voltage

J-Box

Occupancy Sensor

LMRC-212

Dimming

Room

Controller

LMDM-101

Dimming Switch

LMDM-101

Dimming Switch

LMSW-105

Scene Switch

Class 2  0-10 Volt Control Wiring

0-10 Volt

Ballast

0-10 Volt

Ballast

LMRJ Cables

Corner Mount

Occupancy

Sensor

Switch/

Dimmer

Ceiling Mount

Occupancy

Sensor

J Box

To

Load

DLM Local Network

(low voltage, Class 2)

LMRJ cables

LMRC-21x

Room

Controller

To 0-10V 

Dimming Ballast

Daylighting

Sensor

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM 

LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Summary of Contents for Wattstopper LMDM-101-R

Page 1: ...connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring To be connected to a Class 2 power source only Do not reclassify and i...

Page 2: ...s ON load 3 and so forth As each load turns ON note which devices switch buttons sensors etc are showing the blue LED These devices are currently bound to the load that is ON 2 To unbind a switch butt...

Page 3: ...e est optionnel Pour conna tre tous les d tails op rationnels les r glages et les fonctions suppl mentaires du produit consulter le guide d installation du syst me DLM fourni avec les Wattstopper cont...

Page 4: ...t es au dessus de 50 Pour modifier les charges contr l es par le LMDM 101 voir R GLAGE DE L APPAREIL R GLAGE DE L APPAREIL PUSH N LEARN PNL Proc dure de liaison de la charge Un bouton de configuration...

Page 5: ...nnexions haute tension avec le contr leur de pi ce Si les connexions haute tension fonctionnent bien et qu une tension lev e est pr sente v rifier nouveau les connexions du r seau local DLM entre l in...

Page 6: ...Controlador de habitaci n A balasto de regulaci n de 0 a 10 V Sensor de luz de d a INSTRUCCIONES EN ESPA OL ESPECIFICACIONES Voltaje 24 V CC Consumo de corriente 5 mA Suministro de energ a Controlador...

Page 7: ...s de un segundo se encender una carga Esta es la carga N 1 que est vinculada con el bot n interruptor N 1 seg n la configuraci n predeterminada de f brica de Plug n Go El LED azul se mostrar encendid...

Page 8: ...la entrada de 24 V CC al interruptor Conecte un dispositivo DLM diferente en la ubicaci n del interruptor Si el dispositivo no se enciende los 24 V de CC no est n presentes Revise las conexiones de a...

Reviews: