Wattstopper
®
Partition Switch (version 3)
Interrupteur de partition (version 3)
Interruptor de la partición (versión 3)
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
No: 23545– 09/16 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPS-104
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
SPECIFICATIONS
Voltage .............................................................................. 24VDC
Current Consumption .............................................................5mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network .................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000’ max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
This unit is pre-set for Plug n’ Go™ operation,
adjustment is optional.
For full operational details, adjustment and more features
of the product, see the DLM System Installation Guide
provided with Wattstopper room controllers, and also
available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable
regulations, local and NEC codes.
Wire connections shall
be rated suitable for the wire size (lead and building wiring)
employed.
For Class 2 DLM devices and device wiring: To be
connected to a Class 2 power source only. Do not reclassify
and install as Class 1, or Power and Lighting Wiring.
Do not apply cleaning solvent directly onto unit. Apply
cleaning solvent onto a cloth, then wipe the unit to clean it..
MOUNTING THE SWITCH
WARNING:
Do Not Install To Cover a Junction Box having Class 1, 3 or
Power and Lighting Circuits.
BUTTONS AND INDICATORS
Red configuration LED
Green wall status LEDs
Wall status buttons
Configuration button
(behind switch plate)
Each button represents a virtual wall in the DLM space
CONNECTIVITY
The illustration below shows an example of free-topology
wiring. The LMPS switch communicates to all other Digital
Lighting Management devices connected to the low voltage
DLM Local Network, regardless of their position on the DLM
Local Network.
Line
Voltage
Room
Controller
J-Boxes
Switch
Occupancy
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Loads
2
1
Line/Hot
Black wire
Neutral
White wire
Red wire
to Load A (1)
Yellow wire
to Load B (2)
LMRC
102
Partition Switch
MOVABLE WALL/PARTITION EXAMPLE
Each On/Off Wall button on the LMPS-104 represents the state of the
wall (open or closed). In the two partitions example below, Wall 1 and
2 are active (closed) and Wall 3 and 4 are inactive (open). Wall 3 and 4
are unused.
Wall 1
Wall 2
Wall 3
Wall 4
Wall 1
Wall 2
Wall 3
Wall 4
Active (Closed)
Active (Closed)
Room/
Partition 1
Closed
Room/
Partition 2
Closed
Room 3
Movable
Wa
ll
1
Movable
Wa
ll
2
1
2