Button Functions
Press the top of the rocker paddle to turn load(s)
ON
. The blue LED on the paddle
also turns
ON
. Switched loads turn
ON
. Dimmable loads turn
ON
to the last light
level set before they turned
OFF
. Press the bottom of the rocker paddle to turn
load(s)
OFF
.
Dimmable loads ramp down or up in response to pressing and holding the top or
bottom of the paddle.
ON/OFF
loads turn
OFF
when the ramp level dims below 50%,
and turn
ON
when the ramp level rises above 50%. To recall a scene, press one of
the four scene buttons.
Battery Life
To conserve battery life, the LMRH-105 shuts down 5 seconds after the last key
press unless the DLM local network is in configuration mode (Push n’ Learn, PnL).
ADJUSTMENT
The LMRH-105 is pre-set for operation as described in the Default Functionality section under
OPERATION. Adjustment is optional.
A “configuration” button allows access to the Wattstopper Push n’ Learn™ technology to change
the operation of the LMRH-105.
Step 1: Enter Push n’ Learn (PnL).
1.
Locate the configuration button inside the LMRH-105 battery compartment.
2.
Point the LMRH-105 at a DLM IR device.
3.
Press and hold the configuration button until the red LED in the battery compartment begins
blinking (approximately 3 seconds), then release the button.
4.
Make sure the LMRH-105’s red LED continues to blink* then observe the following:
•
The Red LEDs on all other DLM devices on the network start blinking rapidly
(2x/second). The LEDs continue to blink until you exit PnL.
•
All loads on the DLM local network turn
OFF
immediately after entering PnL. After
1 second, load 1 turns
ON
.
Step 2: Load Selection.
1.
A quick press on the LMRH-105’s configuration button turns
OFF
load 1 then turns on the
next load in sequence.
2.
Keep pressing the configuration button to step through all the loads connected to the DLM
local network.*
The blue LED is lit brightly on all switch buttons, scene buttons, dimmer paddles, and sensors that are bound to the load that is
currently
ON
.
*All the blue LEDs on the LMRH-105 flash rapidly if the LMRH-105 does not have proper IR communication with the local network.
Make sure to aim the LMRH-105 toward an
IR-enabled device that is in range when you press the configuration button.
3.
To bind the load to one of the buttons and/or the paddle on the LMRH-105, press the desired button making sure that the LED
turns
ON
brightly.
4. To unbind a load, press the button.
The LED goes dim to indicate the button or paddle on the handheld remote no longer controls this load.
5. A quick press on the configuration button turns
ON
the next load.
6.
Repeat until the paddle and scene switches are bound to the loads you want them to control.
NOTE:
More than one load can be assigned to the paddle or a scene button, and a load can be assigned to multiple devices and
buttons in the DLM network.
Step 3: Exit Push n’ Learn (PnL).
1.
Point the LMRH-105 at a DLM IR device.
2.
Press and hold the LMRH-105 configuration button until the red LED in the battery compartment stops blinking (approximately
3 seconds), then release the button.
The red LED on the local network devices stop blinking to indicate that the network exited PnL.
Point at
DLM Device
Configuration
Button
Red LED
IR Lens
Rocker Paddle
•
Single tap: Bound
loads turn ON to
last light level
• Press and hold:
Raise light level
• Single tap: Bound
loads turn OFF
• Press and hold:
Lower light level
Blue LEDs
Scene Buttons (4)
100%
75%
50%
25%
Scene
1
Scene
2
Scene
3
Scene
4
Default light level